Operation
11/03
SINAMICS G150
6-14
Operating Manual
6.2.3.7
Motor potentiometer
Settings: MENU – Settings – Control Settings
Save motor potentiometer setpoint
(factory setting: no)
•
Yes
: In LOCAL mode, the last setpoint (once you have released the INCREASE
or DECREASE key or confirmed a numeric entry) is saved.
The next time you switch the system on in LOCAL mode, the saved value is
selected. This is also the case if you switched to REMOTE in the meantime or
the power supply was switched off.
When the system is switched from REMOTE to LOCAL mode while the drive is
switched on (motor is running), the actual value that was last present is set as
the output value for the motor potentiometer setpoint and saved.
If the system is switched from REMOTE to LOCAL mode while the drive is
switched off, the motor potentiometer setpoint that was last saved is used.
•
No
: When you switch the system on in LOCAL mode, setpoint 0 is always
selected. When the system is switched from REMOTE to LOCAL mode while
the drive is switched on (motor is running), the actual value that was last
present is set as the output value for the motor potentiometer setpoint.
Motor potentiometer ramp-up time
(factory setting: 20 s)
Motor potentiometer ramp-down time
(factory setting: 30 s)
•
Recommendation
: set as ramp-up/ramp-down time (p1120 / p1121)
6.2.3.8
Operator Input Inhibit / Parameterization Inhibit
To prevent users from accidentally actuating the control keys and changing
parameters, you can activate an operator input / parameterization inhibit using a
key pushbutton. Two key icons appear in the top right of the display when these
inhibit functions are enabled.
Table 6-3
Display for operator input / parameterization inhibit
Inhibit type
Online operation
Offline operation
No inhibit
Operator Input Inhibit
Parameterization Inhibit
Operator input i
parameterization inhibit
Содержание SINAMICS G150
Страница 1: ...Operating Manual Edition 11 2003 sinamics Converter Cabinet Units SINAMICS G150 75 kW to 800 kW ...
Страница 2: ......
Страница 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Страница 136: ...Monitoring Functions and Protective Functions 11 03 SINAMICS G150 9 2 Operating Manual 9 2 Monitoring in preparation ...
Страница 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Страница 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Страница 234: ......
Страница 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Страница 239: ......