11/03
Diagnosis / Faults and Alarms
SINAMICS G150
Operating Manual
10-47
Cause:
DRIVE-CLiQ communication between control unit and at least one other component is
defective.
Fault value
(r0949):
Bit 0 - 7: Number of the affected component
Bit 8 - 31: Reserved
Remedy:
- Check for break in DRIVE-CLiQ or faulty contacts in connector.
- Check 24 V supply of affected component.
- Replace affected component.
Acknowl.: Immediate
F30891
CU DRIVE-CLiQ: Transition to cyclic mode
Reaction: OFF2
Cause:
DRIVE-CLiQ communication between control unit and at least one other component is
defective.
Fault value
(r0949):
Bit 0 - 7: Number of the affected component
Bit 8 - 31: Reserved
Remedy:
- Check firmware states of affected components.
- Replace affected component.
Acknowl.: Immediate
F30899
Power section: unknown fault
Reaction: NONE
Cause:
Version Sensor module does not match
Remedy:
Upgrade drive
Acknowl.: Immediate
A30920
Power section: Temperature sensor error
Cause:
An error has occurred while evaluating the temperature sensor.
Alarm value
(r2124):
1: Wire break or sensor not connected.
2: Short-circuit has occurred.
3: Measured resistance lies below permissible evaluation range.
4: No sensor selected.
5: Internal buffer does not contain the required number of stored values.
6: Negative difference voltage measured.
Remedy:
- Check sensor connection.
- Replace sensor.
A35200
TM: Calibration data
Cause:
Error detected in calibration data of TM.
Alarm value
(r2124):
The hundred thousands and ten thousands places specify the component ID of the TMxx at
which the error occurred.
The thousands place specifies whether an analog input (==0) or analog output (==1) is
affected.
The hundreds place specifies the error type:
0 == No calibration data stored
1 == Offset too large (> 100 mV)
The tens and units places specify the number of the affected input.
Remedy:
Switch the unit off and on again. If the fault persists, replace the module.
F35207
TM: Temperature threshold exceeded
Reaction: OFF2
Cause:
The temperature measured (r4105) during TM temperature measurement has exceeded the
threshold that triggers this fault (p4402[1]). Note that this fault can only be triggered when
temperature evaluation is active (p4100 = 2 for KTY sensor or p4100 = 1 for PTC sensor)
Warning:
Note that fault F35207 only causes the drive to be switched off if at least one BICO
interconnection exists between the drive and TM31.
Fault value
(r0949):
The hundred thousands and ten thousands places indicate the component ID of the TMxx at
which the error occurred.
Remedy:
Cool off temperature sensor.
Содержание SINAMICS G150
Страница 1: ...Operating Manual Edition 11 2003 sinamics Converter Cabinet Units SINAMICS G150 75 kW to 800 kW ...
Страница 2: ......
Страница 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Страница 136: ...Monitoring Functions and Protective Functions 11 03 SINAMICS G150 9 2 Operating Manual 9 2 Monitoring in preparation ...
Страница 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Страница 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Страница 234: ......
Страница 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Страница 239: ......