11/03 Electrical
Installation
SINAMICS G150
Operating Manual
4-27
-A1-X40 15
11
L1
N
-X542
2
3
TM31
"Operation"
-A1-A60
Circuit proposal
-K155
-X155
11
12
Fig. 4-6
Circuit proposal for controlling the auxiliary conductor from within the converter
NOTE
If 230 V AC is applied to the relay outputs, the customer terminal block must also
be grounded via a 6 mm² protective conductor.
4.9.3
Main Circuit-Breaker incl. Fuses/Circuit-Breaker (Option L26)
Description
The main circuit-breaker of cabinet units with an output current of up to 800 A is a
load interruptor with externally mounted fuses. Cabinets with an output current
greater than 800 A are fitted with a circuit-breaker instead of a load interruptor.
Connection
Table 4-18
Terminal block X50 – checkback contact “main circuit-breaker/circuit-breaker
closed“
Terminal Designation
1)
Technical
data
1 NO
2 NC
3 COM
Max. load current: 10 A
Max. switching voltage: 250 V AC
Max. switching capacity: 250 VA
Required minimum load:
≥
1 mA
1)
NO: normally open contact, NC: normally closed contact, COM: mid-position
contact
Max. connectable cross-section: 4 mm² (AWG 10)
Содержание SINAMICS G150
Страница 1: ...Operating Manual Edition 11 2003 sinamics Converter Cabinet Units SINAMICS G150 75 kW to 800 kW ...
Страница 2: ......
Страница 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Страница 136: ...Monitoring Functions and Protective Functions 11 03 SINAMICS G150 9 2 Operating Manual 9 2 Monitoring in preparation ...
Страница 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Страница 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Страница 234: ......
Страница 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Страница 239: ......