![Siemens SINAMICS G150 Скачать руководство пользователя страница 103](http://html.mh-extra.com/html/siemens/sinamics-g150/sinamics-g150_operating-manual_378200103.webp)
11/03
Operation
SINAMICS G150
Operating Manual
6-21
Signal Flow Diagram
Smoothing
p4053
A
D
Type
p4056
S5.0
+
-
AI 0
X521:2
F3505
Wire Break Analog Input
act. V/I
r4052
X521:1
S5.0
S5.1
V
I
I
V
act. value
r4055
Offset
p4063
Scaling
(for p4056 = 3 only)
Fig. 6-9
Signal flow diagram: Analog input 0
Setting Parameters
Setting range: 0 / 2 / 3 / 4 / 5
p4056
Analog input type
Factory setting: 2: 0 ... 20 mA
Setting parameter for the type of the analog inputs on the customer terminal block.
Values: 0: 0 ... 10 V
2: 0 ... 20 mA
3: 4 ... 20 mA with open-circuit monitoring
4: -10 ... +10 V
5: -20 ... +20 mA
Settings 0 and 4: switch S5.0 on the customer terminal block (-A60) must be set to "V".
Settings 2, 3, and 5: switch S5.0 on the customer terminal block (-A60) must be set to "I".
Setting 3 with open-circuit monitoring: fault F3505 is triggered if the input current is less than 2 mA.
r4052
Current input voltage/current
Unit: V or mA
The current input voltage is displayed in V when the analog input is set as a voltage input (p4056 = 0 / 4)
and switch S5.0 is set to "V".
The current input current is displayed in mA when the analog input is set as a current input (p4056 = 2 / 3
/ 5) and switch S5.0 is set to "I".
Setting range: -20.000 ... 20.000 V or mA
p4063
Analog input offset
Factory setting: 0.000 V or mA
Setting parameter for the offset added to the input signal upstream of the scaling characteristic.
The unit is V when the analog input is set as a voltage input (p4056 = 0 / 4) and switch S5.0 is set to "V".
The unit is mA when the analog input is set as a current input (p4056 = 2 / 3 / 5) and switch S5.0 is
set to "I".
Содержание SINAMICS G150
Страница 1: ...Operating Manual Edition 11 2003 sinamics Converter Cabinet Units SINAMICS G150 75 kW to 800 kW ...
Страница 2: ......
Страница 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Страница 136: ...Monitoring Functions and Protective Functions 11 03 SINAMICS G150 9 2 Operating Manual 9 2 Monitoring in preparation ...
Страница 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Страница 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Страница 234: ......
Страница 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Страница 239: ......