11/03
Output Terminals
SINAMICS G150
Operating Manual
8-7
Selection of possible connections for the digital outputs
Signal
Bit in status
word 1
Parameter
1 = Ready to start
0
r0889.0
1 = Ready to operate (DC link loaded, pulses blocked)
1
r0889.1
1 = Operation enabled (drive follows n_setp)
2
r0889.2
1 = Fault present
3
r2139.3
0 = Coast to stop active (OFF2)
4
r0889.4
0 = Emergency stop active (OFF3)
5
r0889.5
1 = Power-on disable
6
r0889.6
1 = Alarm present
7
r2139.7
1 = Speed setpoint/actual deviation within tolerance band (p2163, p2166)
8
r2197.7
1 = Control required to PLC
9
r0899.9
1 = f or n comparison value reached or exceeded (p2141, p2142)
10
r2199.1
1 = I, M, or P limit reached (p0640, p1520, p1521)
11
r1407.7
reserved
12
0 = Alarm motor overtemperature (A7910)
13
r2129.14
reserved
14
0 = Alarm thermal overload in power section (A5000)
15
r2129.15
1 = Pulses enabled (inverter is clocking, drive is carrying current)
r0899.11
1 = n_act
≤
p2155
r2197.1
1 = n_act > p2155
r2197.2
1 = Ramp-up/ramp-down completed
r2199.5
1 = n_act < p2161 (preferably as n_min or n=0 message)
r2199.0
1 = Torque setpoint < p2174
r2198.10
1 = LOCAL mode active (control via operator panel)
r0807.0
0 = Motor blocked
r2198.6
Active command data set (CDS):
0 = CDS 0 (PROFIBUS), 1 = CDS 1 (terminal block)
r0836.0
Содержание SINAMICS G150
Страница 1: ...Operating Manual Edition 11 2003 sinamics Converter Cabinet Units SINAMICS G150 75 kW to 800 kW ...
Страница 2: ......
Страница 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Страница 136: ...Monitoring Functions and Protective Functions 11 03 SINAMICS G150 9 2 Operating Manual 9 2 Monitoring in preparation ...
Страница 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Страница 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Страница 234: ......
Страница 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Страница 239: ......