Maintenance and Servicing
SINAMICS G150
Operating Manual
11-9
Upgrading the Firmware for the Cabinet Unit Components
Select the node number of the power section
The node number of the power section is "2".
p7828 = 3
p7828 = 2
Access level "Expert"
Set the "Expert" access level on the operator panel
<Key pushbutton> - <Access level> - Enter the activation code
"47"
p7829 = 1
POWER ON
p7829 = 1
Upgrade the firmware
This process lasts a few minutes. It has been completed
successfully when p7829 automatically switches to "0".
Select the node number of the customer terminal block
The node number of the customer terminal block (-A60) is "3".
Fault during the upgrade
Faults that occur while the firmware is being upgraded are indicated by fault F1005 and a
fault value.
Upgrade the firmware
This process lasts a few minutes. It has been completed
successfully when p7829 automatically switches to "0".
POWER ON
To activate the new firmware, switch the power supply off and
then on.
Fig. 11-2
Upgrading the cabinet unit firmware
NOTE
Once the firmware has been upgraded, the firmware for the operator panel must
also be upgraded.
Содержание SINAMICS G150
Страница 1: ...Operating Manual Edition 11 2003 sinamics Converter Cabinet Units SINAMICS G150 75 kW to 800 kW ...
Страница 2: ......
Страница 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Страница 136: ...Monitoring Functions and Protective Functions 11 03 SINAMICS G150 9 2 Operating Manual 9 2 Monitoring in preparation ...
Страница 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Страница 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Страница 234: ......
Страница 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Страница 239: ......