Technical Data
11/03
SINAMICS G150
12-20
Operating Manual
Table 12-21 Version C, 660 V – 690 V, part 5
Category Unit
Order no.
6SL3710-
1GH38-1CA0
Rated motor output
kW
800
Rated connection voltage
V
3 AC 660 V to 690 V ±10 % (-15 % < 1 min)
Rated input current
A
852
Rated output current
A
810
Base load current
A
790
Power loss
kW
14.7
Cooling air requirement
m³/s
1.48
Sound pressure level at 50/60
Hz
dB(A) 72/75
Power connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
mm
2
mm
2
4 x 150
4 x (400)
8 x 240
8 x (600)
M12 (4 holes)
Motor connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
mm
2
mm
2
4 x 150
4 x (400)
6 x 240
6 x (600)
M12 (3 holes)
Protective earth connection
Fastening screw
M12 (18 holes)
Approx. weight (standard
version)
kg 980
Dimensions (w x h x d)
mm
1000 x 2000 x 600
Recommended protection
Cond./semi-cond. protection
Rated current
Size to DIN 43 620-1
A
Circuit-breaker
Содержание SINAMICS G150
Страница 1: ...Operating Manual Edition 11 2003 sinamics Converter Cabinet Units SINAMICS G150 75 kW to 800 kW ...
Страница 2: ......
Страница 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Страница 136: ...Monitoring Functions and Protective Functions 11 03 SINAMICS G150 9 2 Operating Manual 9 2 Monitoring in preparation ...
Страница 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Страница 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Страница 234: ......
Страница 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Страница 239: ......