Diagnosis / Faults and Alarms
11/03
SINAMICS G150
10-28
Operating Manual
Cause:
The selected trigger signal is invalid. Possible causes:
- No trigger signal specified (required only if p4710 not equal to 1)
- Specified signal does not exist
- Specified signal cannot be used as a trigger signal for the trace.
See also: p4711
Remedy:
Specify a valid trigger signal (p4711).
See also: p4711
A2063
Trace: Invalid data type
Cause:
The data type specified for signal selection via the physical address is invalid.
See also: p4711, p4730, p4731, p4732, p4733
Remedy:
Use a valid data type.
A2070
Trace: Parameter cannot be changed
Cause:
When the trace is active (p4700 = 1), you cannot change its parameters.
See also: p4700, p4710, p4711, p4712, p4713, p4714, p4715, p4716, p4720, p4721, p4722,
p4730, p4731, p4732, p4733, p4755, p4780, p4781, p4782, p4783, p4789
Remedy:
- Stop the trace before parameterization (p4800 = 0).
- If necessary, start the trace (p4700 = 1).
A2075
Trace: Pretrigger time too long
Cause:
The set pretrigger time must be smaller than the trace duration.
See also: p4721, p4722
Remedy:
Check the pretrigger time and adjust if necessary.
A2099
Trace: Out of memory
Cause:
The remaining memory on the control unit is not sufficient for the trace function.
Note:
The available memory on the control unit can be read via r4795.
The memory requirement of the trace is displayed in r4708.
Remedy:
Reduce memory requirement as follows:
- Reduce the trace duration
- Increase the trace clock cycle
- Reduce the number of signals to be traced
See also: r4708, r4799
F3500
TM: Initialization
Reaction: OFF2
Cause:
An internal software error occurred while initializing the TM, the CU terminals, or the TB30.
Fault value
(r0949):
The thousands digit = 1... 3
Ones, tens and hundreds places indicate the component ID of the affected TM.
Remedy:
Switch the power supply to the CU off and on again. Check DRIVE-CLiQ connection. The
TM should be connected directly to a DRIVE-CLiQ port at the CU. If the error recurs, replace
the TM module.
Acknowl.: Immediate
F3505
TM: Analog Input Wire Break
Reaction: OFF2
Cause:
Input current of analog input of TM has exceeded the threshold parameterized in p4061[x].
This fault can only occur if p4056[x] = 3 (4... 20mA with monitoring).
Index x = 0: analog input 0 (X522.1 to .3)
Index x = 1: analog input 1 (X522.4 to .5)
Fault value
(r0949):
The ones, tens and hundreds places indicate the component ID (r0151) of the affected TM.
The thousands place indicates the affected analog input : 0: analog input 0 (AI0), 1: analog
input 1 (AI1)
Remedy:
Check connection to signal source for interruptions. Check level of induced current (infeed
signal may be too low). Ensure that the input has a load resistance of 250Ohm. The input
current measured by the TM can be output in r4052[x].
Acknowl.: Immediate
Содержание SINAMICS G150
Страница 1: ...Operating Manual Edition 11 2003 sinamics Converter Cabinet Units SINAMICS G150 75 kW to 800 kW ...
Страница 2: ......
Страница 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Страница 136: ...Monitoring Functions and Protective Functions 11 03 SINAMICS G150 9 2 Operating Manual 9 2 Monitoring in preparation ...
Страница 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Страница 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Страница 234: ......
Страница 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Страница 239: ......