Diagnosis / Faults and Alarms
11/03
SINAMICS G150
10-14
Operating Manual
Reaction: NONE
Cause:
Defective files detected on CompactFlash Card during startup.
Remedy:
- Repair files
- Save parameters (p0977).
- Fault can be acknowledged after saving
Acknowl.: Immediate
A1100
CU: CompactFlash Card removed
Cause:
The CompactFlash card (non-volatile memory) was removed during operation.
Caution:
The CompactFlash card must not be removed or inserted when the system is live.
Remedy:
- Switch off the drive system.
- Reinsert the CompactFlash Card that is suitable for the plant.
- Switch the drive system back on.
F1105
CU: Insufficient memory
Reaction: OFF1
Cause:
Too many functions, data sets or drives are configured on this control unit.
Remedy:
- Change configuration on this control unit.
- Use a different control unit.
Acknowl.: Immediate
F1107
CU: Save to CompactFlash Card failed
Reaction: NONE
Cause:
Unable to save data on CompactFlash Card.
- CompactFlash Card defective.
- Insufficient memory on CompactFlash Card.
Remedy:
- Try again.
- Use another CompactFlash card.
Acknowl.: Immediate
F1110
CU: Only one SINAMICS G at a time may be operated at a Control Unit.
Reaction: NONE
Cause:
More than one drive of type SINAMICS G is in operation with the control unit.
Remedy:
Only one drive of type SINAMICS G is permitted.
Acknowl.: Immediate
F1111
CU: Drive types SINAMICS S/G cannot be combined at a CU
Reaction: NONE
Cause:
The drive units SINAMICS S and G are operating together on one control unit.
Remedy:
You may only operate equipment of one drive type on one CU.
Acknowl.: Immediate
F1205
CU: Time slice overflow
Reaction: OFF2
Cause:
Insufficient processing time for existing topology.
Remedy:
Reduce the number of axes or increase the sampling times.
Acknowl.: POWER
ON
F1210
CU: Basic clock cycle does not match DRIVE-CLiQ clock cycle
Reaction: NONE
Cause:
The parameter for selecting the basic clock cycle does not match the drive topology. Drives
connected to the same DRIVE-CLiQ port of the control unit have been assigned different
basic clock cycles.
See also: p0111
Remedy:
The same basic clock must be selected for drives connected to one and the same. DRIVE-
CLiQ port of the CU (e.g. in series).
See also: p0111
Acknowl.: Immediate
Содержание SINAMICS G150
Страница 1: ...Operating Manual Edition 11 2003 sinamics Converter Cabinet Units SINAMICS G150 75 kW to 800 kW ...
Страница 2: ......
Страница 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Страница 136: ...Monitoring Functions and Protective Functions 11 03 SINAMICS G150 9 2 Operating Manual 9 2 Monitoring in preparation ...
Страница 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Страница 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Страница 234: ......
Страница 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Страница 239: ......