![Siemens SINAMICS G150 Скачать руководство пользователя страница 191](http://html.mh-extra.com/html/siemens/sinamics-g150/sinamics-g150_operating-manual_378200191.webp)
11/03
Diagnosis / Faults and Alarms
SINAMICS G150
Operating Manual
10-49
Cause:
Checksum error encountered while reading out program memory on TM.
Remedy:
- Check whether the permissible ambient temperature has been observed for the TM .
- Replace TM.
A35805
TM: Checksum EPROM not correct
Cause:
Internal parameter data corrupted.
Remedy:
- Check whether the permissible ambient temperature has been observed for the module.
- Replace module.
A35806
TM: Initialization
Cause:
An error occurred on the TM during initialization.
Remedy:
none
A35807
TM: Process control Watchdog
Cause:
Error timeout Process control on TM
Remedy:
Replace TM.
F35820 -
F35825
TM DRIVE-CLiQ: Telegram faulted
Reaction: OFF2
Cause:
There is a DRIVE-CLiQ communication error between the control unit and the affected
terminal module.
Remedy:
- Check cabinet design and cabling for EMC conformity.
- Replace affected component.
See also: p9916
Acknowl.: Immediate
F35826
F35827
TM DRIVE-CLiQ: fault in cyclic data transfer
Reaction: OFF2
Cause:
There is a DRIVE-CLiQ communication error between the control unit and the affected
terminal module.
Remedy:
- Check firmware states of affected components.
- Replace Control Unit.
Acknowl.: Immediate
F35828
TM DRIVE-CLiQ: Receive ALARM bit
Reaction: OFF2
Cause:
There is a DRIVE-CLiQ communication error between the control unit and the affected
terminal module.
Remedy:
Replace affected component.
Acknowl.: Immediate
F35829
F35830
TM DRIVE-CLiQ: Fault in cyclic data transfer
Reaction: OFF2
Cause:
There is a DRIVE-CLiQ communication error between the control unit and the affected
terminal module.
Remedy:
- Check firmware states of affected components.
- Replace affected component.
See also: p9916
Acknowl.: Immediate
F35831
TM DRIVE-CLiQ: Telegram faulted
Reaction: OFF2
Cause:
There is a DRIVE-CLiQ communication error between the control unit and the affected
terminal module.
Remedy:
Replace affected component.
Acknowl.: Immediate
Содержание SINAMICS G150
Страница 1: ...Operating Manual Edition 11 2003 sinamics Converter Cabinet Units SINAMICS G150 75 kW to 800 kW ...
Страница 2: ......
Страница 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Страница 136: ...Monitoring Functions and Protective Functions 11 03 SINAMICS G150 9 2 Operating Manual 9 2 Monitoring in preparation ...
Страница 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Страница 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Страница 234: ......
Страница 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Страница 239: ......