Diagnosis / Faults and Alarms
11/03
SINAMICS G150
10-26
Operating Manual
Cause:
Synchronization of the internal clock cycle with the global control telegram has failed. The
internal clock cycle exhibits an unexpected shift.
Remedy:
Siemens-internal
Acknowl.: Immediate
A2000
Function generator: Start not possible
Cause:
The function generator has already been started.
Remedy:
Stop and, if necessary, restart the function generator.
See also: p4800
A2005
Function generator: Specified drive does not exist
Cause:
The drive object specified for connection does not exist.
Remedy:
Use an existing drive object with the appropriate number.
See also: p4815
A2006
Function generator: No drive specified for connection
Cause:
No drive specified for connection in p4815.
See also: p4815
Remedy:
At least one drive must be specified for connection in p4815.
See also: p4815
A2007
Function generator: Drive for connection is not a servo drive
Cause:
The drive object specified for connection is not a SERVO.
See also: p4815
Remedy:
Use a SERVO drive object with the appropriate number.
A2010
Function generator: Speed setpoint of a drive not equal to zero
Cause:
The speed setpoint of a drive specified for connection is greater than the value set via p1226
for zero speed detection.
Alarm value
(r2124):
Number of the affected drive object.
Remedy:
Set the speed setpoints of all drives specified for connection to zero.
A2011
Function generator: Speed value of a drive not equal to zero
Cause:
The actual speed value of a drive specified for connection is greater than the value set via
p1226 for zero speed detection.
Alarm value
(r2124):
Number of the affected drive object.
Remedy:
Before you start the function generator, set the drive speed to zero.
A2020
Function generator: Parameter cannot be changed
Cause:
No configuration parameter may be changed when the function generator is active
(p4800=1).
See also: p4810, p4812, p4813, p4815, p4820, p4821, p4822, p4823, p4824, p4825, p4826,
p4827, p4828, p4829
Remedy:
- Stop the function generator before parameterization (p4800 = 0).
- If necessary, start the function generator (p4800 = 1).
See also: p4800
A2025
Function generator: Period too short
Cause:
The value for the pulse duration is too small.
See also: p4821
Remedy:
Check and adapt the value for the period.
See also: p4821
A2026
Function generator: Pulse width too long
Cause:
The set pulse width is too long.
See also: p4821, p4822
Remedy:
The pulse width must be shorter than the period. Reduce the pulse width.
See also: p4822
Содержание SINAMICS G150
Страница 1: ...Operating Manual Edition 11 2003 sinamics Converter Cabinet Units SINAMICS G150 75 kW to 800 kW ...
Страница 2: ......
Страница 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Страница 136: ...Monitoring Functions and Protective Functions 11 03 SINAMICS G150 9 2 Operating Manual 9 2 Monitoring in preparation ...
Страница 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Страница 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Страница 234: ......
Страница 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Страница 239: ......