![Siemens SINAMICS G150 Скачать руководство пользователя страница 214](http://html.mh-extra.com/html/siemens/sinamics-g150/sinamics-g150_operating-manual_378200214.webp)
Technical Data
11/03
SINAMICS G150
12-6
Operating Manual
Table 12-7
Version A, 380 V – 480 V, part 2
Category Unit
Order no.
6SL3710-
1GE33-8AA0 1GE35-0AA0 1GE36-1AA0
Rated motor output
kW
200
250
315
Rated connection voltage
V
3 AC 380 V to 480 V ±10 % (-15 % < 1 min)
Rated input current
A
405
519
639
Rated output current
A
380
490
605
Base load current
A
370
477
590
Power loss
kW
5.3
6.4
8.2
Cooling air requirement
m³/s
0.36
0.36
0.78
Sound pressure level at 50/60
Hz
dB(A) 69/73
69/73
70/73
Power connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
mm
2
mm
2
2 x 120
2 x (300)
4 x 240
4 x (600)
M12 (2 holes)
2 x 185
2 x (500)
4 x 240
4 x (600)
M12 (2 holes)
2 x 240
2 x (600)
4 x 240
4 x (600)
M12 (2 holes)
Motor connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
mm
2
mm
2
2 x 120
2 x (300)
2 x 150
2 x (400)
M12 (2 holes)
2 x 185
2 x (500)
2 x 240
2 x (600)
M12 (2 holes)
2 x 240
2 x (600)
4 x 240
4 x (600)
M12 (2 holes)
Protective earth connection
Fastening screw
M12 (2 holes)
M12 (2 holes)
M12 (2 holes)
Approx. weight (standard
version)
kg 480
480
860
Dimensions (w x h x d)
mm
1000 x 2000 x 600 1000 x 2000 x 600 1200 x 2000 x 600
Recommended protection
Conductor protection
(with option L26)
Rated current
Size to DIN 43 620-1
Cond./semi-cond. protection
(without option L26)
Rated current
Size to DIN 43 620-1
A
A
3NA3 365
500
3
3NE1 334-2
500
2
3NA3 372
630
3
3NE1 436-2
630
3
3NA3 475
800
4
3NE1 438-2
800
3
Содержание SINAMICS G150
Страница 1: ...Operating Manual Edition 11 2003 sinamics Converter Cabinet Units SINAMICS G150 75 kW to 800 kW ...
Страница 2: ......
Страница 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Страница 136: ...Monitoring Functions and Protective Functions 11 03 SINAMICS G150 9 2 Operating Manual 9 2 Monitoring in preparation ...
Страница 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Страница 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Страница 234: ......
Страница 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Страница 239: ......