Operation
11/03
SINAMICS G150
6-20
Operating Manual
6.3.2 Analog
Inputs
Description
The customer terminal block features two analog inputs for specifying setpoints via
current or voltage signals. In the factory setting, analog input 0 (terminal X521:1/2)
is used as the current input.
Prerequisite
p1070 = r4055[00]
Main setpoint is specified by analog input 0
<MENU> - <parameterization> - <all parameters> - Select
p1070 and set to r4055 - Select index [00]
Proposed Connection Assignment
4
3
2
1
5
6
=
~~
=
M
~
X521
~~
8
7
S5.0
M
+
1
N10
M
P10
AI 1-
AI 1+
AI 0+
AI 0-
DI 4
4
3
2
1
5
6
X520
M
M1
DI 3
DI 2
DI 1
DI 0
1
X530
X540
-A10 (CU 320)
-A60 (TM31)
ON/OFF1
Fault ack.
PROFIBUS/
terminal block
1: Terminal
block
user wiring
20 mA = n max
(p2000)
Fig. 6-8
Proposed connection assignment
Содержание SINAMICS G150
Страница 1: ...Operating Manual Edition 11 2003 sinamics Converter Cabinet Units SINAMICS G150 75 kW to 800 kW ...
Страница 2: ......
Страница 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Страница 136: ...Monitoring Functions and Protective Functions 11 03 SINAMICS G150 9 2 Operating Manual 9 2 Monitoring in preparation ...
Страница 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Страница 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Страница 234: ......
Страница 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Страница 239: ......