Table 12-11 Version C, 380 V – 480 V, part 3
Category Unit
Order no.
6SL3710-
1GE37-5CA0 1GE38-4CA0 1GE41-0CA0
Rated motor output
kW
400
450
560
Rated connection voltage
V
3 AC 380 V to 480 V ±10 % (-15 % < 1 min)
Rated input current
A
785
883
1034
Rated output current
A
745
840
985
Base load current
A
725
820
960
Power loss
kW
9.6
10.1
14.4
Cooling air requirement
m³/s
0.78
0.78
1.48
Sound pressure level at 50/60
Hz
dB(A) 70/73
70/73
72/75
Power connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
mm
2
mm
2
2 x 300
2 x (800)
8 x 240
8 x (600)
M12 (4 holes)
4 x 150
4 x (400)
8 x 240
8 x (600)
M12 (4 holes)
4 x 185
4 x (500)
8 x 240
8 x (600)
M12 (4 holes)
Motor connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
mm
2
mm
2
2 x 300
2 x (800)
8 x 240
8 x (600)
M12 (4 holes)
4 x 150
4 x (400)
8 x 240
8 x (600)
M12 (4 holes)
4 x 185
4 x (500)
8 x 240
8 x (600)
M12 (4 holes)
Protective earth connection
Fastening screw
M12 (8 holes)
M12 (8 holes)
M12
(10 holes)
Approx. weight (standard
version)
kg 670
670
980
Dimensions (w x h x d)
mm
600 x 2000 x 600
600 x 2000 x 600
1000 x 2000 x 600
Recommended protection
Cond./semi-cond. protection
Rated current
Size to DIN 43 620-1
A
3NE1 448-2
850
3
Circuit-breaker
Circuit-breaker
Содержание SINAMICS G150
Страница 1: ...Operating Manual Edition 11 2003 sinamics Converter Cabinet Units SINAMICS G150 75 kW to 800 kW ...
Страница 2: ......
Страница 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Страница 136: ...Monitoring Functions and Protective Functions 11 03 SINAMICS G150 9 2 Operating Manual 9 2 Monitoring in preparation ...
Страница 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Страница 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Страница 234: ......
Страница 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Страница 239: ......