11/03
Diagnosis / Faults and Alarms
SINAMICS G150
Operating Manual
10-29
F3590
TM: Module not ready
Reaction: OFF2
Cause:
The affected terminal module is not sending a ready signal or valid cyclic data.
Fault value
(r0949):
Drive object number
Remedy:
- Check the 24 V supply.
- Check the DRIVE CliQ connection.
Acknowl.: Immediately
A5000
Power section: Overtemperature heatsink
Cause:
Warning threshold for overtemperature on inverter heatsink has been reached. The reaction
is set in p0290.
Remedy:
Check the following points:
- Does the ambient temperature lie within the defined limits?
- Are the load conditions and the duty cycle configured correctly?
- Has the cooling failed?
A5001
Power section: Overtemperature Chip
Cause:
Warning threshold for overtemperature of power semiconductors of inverter has been
reached. The reaction is set in p0290.
Remedy:
Check the following points:
- Does the ambient temperature lie within the defined limits?
- Are the load conditions and the duty cycle configured correctly?
- Has the cooling failed?
- Pulse frequency too high?
A5002
Power section: Overtemperature Intake air
Cause:
Warning threshold for inlet air overtemperature has been reached. The reaction is set in
p0290.
Remedy:
Check the following points:
- Does the ambient temperature lie within the defined limits?
- Has the cooling failed?
A5003
Power section: Overtemperature Electronic module
Cause:
Warning threshold for overtemperature of Ebox has been reached. The reaction is set in
p0290.
Remedy:
Check the following points:
- Does the ambient temperature lie within the defined limits?
- Has the cooling failed?
A5004
Power section: Over temperature DC converter
Cause:
Warning threshold for rectifier overtemperature has been reached. The reaction is set in
p0290.
Remedy:
Check the following points:
- Does the ambient temperature lie within the defined limits?
- Are the load conditions and the duty cycle configured correctly?
- Has the cooling failed?
- Line phase failure?
- Branch of input DC converter defective?
F7011
Drive: Motor Overtemperature
Reaction: OFF2
Cause:
Motor temperature has reached the fault threshold parameterized in (p0605).
- Motor is overloaded.
- Motor ambient temperature too high.
Remedy:
- Reduce motor load.
- Check ambient temperature.
Acknowl.: Immediate
Содержание SINAMICS G150
Страница 1: ...Operating Manual Edition 11 2003 sinamics Converter Cabinet Units SINAMICS G150 75 kW to 800 kW ...
Страница 2: ......
Страница 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Страница 136: ...Monitoring Functions and Protective Functions 11 03 SINAMICS G150 9 2 Operating Manual 9 2 Monitoring in preparation ...
Страница 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Страница 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Страница 234: ......
Страница 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Страница 239: ......