Operation
11/03
SINAMICS G150
6-26
Operating Manual
Signal Flow Diagram
0 0
0 1
1 0
1 1
Fixed speed setpoint 03
p1003
Fixed speed setpoint 02
p1002
Fixed speed setpoint 01
p1001
-X530:4
-X530:3
0.000
Fixed speed setpoint
active
r1024
Fig. 6-15
Signal flow diagram: Fixed speed setpoints
Setting Parameters
Setting range: -210000.000 ... +210000.000 1/min
p1001
Fixed speed setpoint 01
Factory setting: 300,000 1/min
Entry for the first fixed speed setpoint.
Setting range: -210000.000 … +210000.000 1/min
p1002
Fixed speed setpoint 02
Factory setting: 600.000 1/min
Entry for the second fixed speed setpoint.
Setting range: -210000.000 ... +210000.000 1/min
p1003
Fixed speed setpoint 03
Factory setting: 1500.000 1/min
Entry for the third fixed speed setpoint.
r1024
Fixed speed setpoint active
Unit: 1/min
Display the active fixed speed setpoint.