Electrical Installation
11/03
SINAMICS G150
4-8
Operating Manual
Shield Gaps
•
Bridge shield gaps (at terminals, circuit-breakers, contactors, and so on) with
minimum impedance and the greatest possible surface area.
Using Large Cross-Sections
•
Use underground and grounding cables with large cross-sections or, better still,
with litz wires or flexible cables.
Laying the Motor Supply Cable Separately
•
The distance between the motor supply cable and signal cable should be > 20
cm. Do not lay power cables and motor supply cables in parallel to each other.
Securing the Potential to Ground Between Modules with Widely Differing
Interference Potential
•
Lay an equalizing cable parallel to the control cable (the cable cross-section
must be at least 16 mm²).
•
If relays, contactors, and inductive or capacitive loads are connected, the
switching relays or contactors must be provided with anti-interference elements.
Cable Installation
•
Cables that are subject to or sensitive to interference should be laid as far apart
from each other as possible.
•
Noise immunity increases when the cables are laid close to the ground
potential. For this reason, you are advised to lay these cables in corners and on
the ground potential.
•
Ground the spare cables at at least one end.
•
Long cables should be shortened or laid in noise resistant areas to avoid
additional connecting points.
•
Conductors or cables that carry signals of different classes must cross at right
angles, especially if they carry sensitive signals that are subject to interference.
–
Class 1:
unshielded cables for
≤
60 V DC
unshielded cables for
≤
25 V AC
shielded analog signal cables
shielded bus and data cables
operator panel interface, incremental/absolute encoder lines
–
Class 2:
unshielded cables for > 60 V DC and
≤
230 V DC
unshielded cables for > 25 V AC and
≤
230 V AC
–
Class 3:
unshielded cables for > 230 V AC/DC and
≤
1000 V AC/DC
Содержание SINAMICS G150
Страница 1: ...Operating Manual Edition 11 2003 sinamics Converter Cabinet Units SINAMICS G150 75 kW to 800 kW ...
Страница 2: ......
Страница 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Страница 136: ...Monitoring Functions and Protective Functions 11 03 SINAMICS G150 9 2 Operating Manual 9 2 Monitoring in preparation ...
Страница 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Страница 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Страница 234: ......
Страница 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Страница 239: ......