Diagnosis / Faults and Alarms
SINAMICS G150
Operating Manual
10-41
Cause:
Unable to precharge DC link of power section within the expected time.
- Power supply too low.
- Defective line phase.
- Short-circuit or ground fault in DC link.
- Precharging circuit defective.
See also: p0210
Remedy:
- Check line voltage.
- Check line connection.
See also: p0210
Acknowled.: Immediate
F30029
Power section: Motor/line filter Temperature sensor Wire break
Reaction: NONE
Cause:
Connection between power section and motor/line filter temperature sensor is interrupted.
Remedy:
Check temperature sensor for correct connection.
Acknowl.: Immediate
F30030
Power section: Motor/line filter temperature sensor short-circuit
Reaction: NONE
Cause:
Power section motor/line filter short- circuit in temperature sensor.
Remedy:
Check temperature sensor for correct connection.
Acknowl.: Immediate
A30031
Power section: Hardware current limit tripped in phase R
Cause:
Current in Phase R has reached permissible current limit of power section. Pulsing is
blocked for one pulse period.
- Control incorrectly parameterized.
- Fault in motor or in power lines.
- Power lines exceed maximum permissible length.
- Motor load too high.
- Power section defective.
Remedy:
- Check motor data.
- Check motor switching mode (star/delta)
- Check motor load.
- Check power line connections.
- Check power lines for short-circuit or ground fault.
- Check the length of the power lines.
A30032
Power section: Hardware current limit tripped in phase S
Cause:
Current in Phase S has reached permissible current limit of power section. Pulsing is
blocked for one pulse period.
- Control incorrectly parameterized.
- Fault in motor or in power lines.
- Power lines exceed maximum permissible length.
- Motor load too high.
- Power section defective.
Remedy:
- Check motor data.
- Check motor switching mode (star/delta)
- Check motor load.
- Check power line connections.
- Check power lines for short-circuit or ground fault.
- Check length of power lines.
A30033
Power section: Hardware current limit tripped in phase T
Содержание SINAMICS G150
Страница 1: ...Operating Manual Edition 11 2003 sinamics Converter Cabinet Units SINAMICS G150 75 kW to 800 kW ...
Страница 2: ......
Страница 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Страница 136: ...Monitoring Functions and Protective Functions 11 03 SINAMICS G150 9 2 Operating Manual 9 2 Monitoring in preparation ...
Страница 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Страница 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Страница 234: ......
Страница 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Страница 239: ......