Draining condensation
Under the following conditions it is possible that condensate may accumulate within the
machine:
● Wide fluctuations in the ambient temperature, such as direct sunshine combined with high
atmospheric humidity
● Intermittent operation or load fluctuations during operation
NOTICE
Damage due to condensate
If the stator winding is damp, its insulation resistance will be reduced. This can result in
voltage flashovers, which can destroy the winding. Condensate can also cause rust to
form within the machine.
Ensure that condensate can drain away.
Depending on the type of installation, the water drainage holes are located at the bottom:
Allow the condensation water to discharge for vertical placement
In the DE bearing shield, water drain holes are located in the area of the mounting feet or
opposite the regreasing system. They are sealed with screw plugs.
Figure 5-2
Condensation water drain for vertical mounting
Assembly
5.2 Lift the machine to where it will be installed, and position it
SIMOTICS FD 1MH1
70
Operating Instructions 08/2017
Содержание SIMOTICS FD 1LL1
Страница 2: ...18 08 2017 17 24 V10 00 ...
Страница 32: ...Description 3 1 Comparison of IEC and GOST standards SIMOTICS FD 1MH1 32 Operating Instructions 08 2017 ...
Страница 58: ...Preparations for use 4 19 Converter operation SIMOTICS FD 1MH1 58 Operating Instructions 08 2017 ...
Страница 104: ...Electrical connection 6 6 Connecting the auxiliary circuits SIMOTICS FD 1MH1 104 Operating Instructions 08 2017 ...
Страница 120: ...Start up 7 10 Setting the motor parameters at the converter SIMOTICS FD 1MH1 120 Operating Instructions 08 2017 ...
Страница 176: ...Disposal 11 4 Disposal of components SIMOTICS FD 1MH1 176 Operating Instructions 08 2017 ...
Страница 178: ...Service and Support SIMOTICS FD 1MH1 178 Operating Instructions 08 2017 ...
Страница 182: ...Quality documents SIMOTICS FD 1MH1 182 Operating Instructions 08 2017 ...
Страница 187: ......