Inserting a DP device
PROFIBUS devices can be inserted directly into the PROFIBUS DP master system.
1. Select the device you require under "PROFIBUS DP" in the hardware catalog and drag it
onto the DP master system.
Inserting a DP remote I/O system (distributed I/O)
Integration is described based on the example of ET 200iSP .
1. Place the head-end station "IM152-1" you have selected from the hardware catalog under
"PROFIBUS DP > ET200iSP" at the DP master system.
The slots of the head-end station are displayed in the detail view in the table below the
graphic.
2. You can insert the required analog and digital modules in slot 4 and higher.
Inserting a PA device at a DP/PA coupler
1. Select a device in the PROFIBUS-PA folder of the hardware catalog.
This can be, for example, a SITRANS P pressure transmitter listed under "PROFIBUS-PA
> Siemens > Sensors > Pressure > SITRANS P" or a device profile listed under "PROFIBUS-
PA > Other".
2. Position it at the PROFIBUS DP master system.
You have to select the device for some objects. You can find information on this in the
section ""Insert Object - Assign Device Type" dialog box (Page 79)".
Note
The DP/PA coupler does not need to be configured; you only need to set an appropriate
bus transmission rate (for example, 45.45 kbps for the Siemens coupler) for the DP master
system.
Inserting a PA device at a DP/PA-Link
1. Place the "IM 153-2" you have selected from the hardware catalog under "PROFIBUS DP
> DP/PA-Link" at the DP master system. (The IM 153-2 replaces the IM 157, but both types
can be used as PROFIBUS-Link ).
HW Config creates a PA master system for the DP/PA-Link .
2. Drag-and-drop the PA devices to this PA master system.
For certain objects it is necessary to select the device. You can find information on this in
the section ""Insert Object - Assign Device Type" dialog box (Page 79)".