Commissioning
7.3 Connecting and setting up the reader using the PST
SIMATIC MV500
92
Operating Instructions, 06/2018, C79000-G8976-C494-01
Device flash test and reset
Device flash test
If several readers are connected to the network/PC, it is possible to make the LK LEDs of the
device selected in the output window flash. Using the device flash test, you can identify the
required reader quickly and simply.
Follow the steps below to identify the relevant reader using the flash test:
1.
In the menu bar, select the menu command "Network > Browse".
2.
Select the required module from the device list.
3.
In the menu bar, select the menu command "Module > Flash".
4.
Click on the "Start" button.
Reaction: The LK LED flashes at a frequency of 1 Hz (1 s) on the selected reader.
5.
Click the "Stop" button to stop the flashing.
Reset
You can also use the Primary Setup Tool to reset the communication parameters (SNMP, IP
address) of the reader. To do so, select the reader and the menu command "Module >
Reset".
Note that, for safety reasons, a reset cannot be performed in processing mode (RUN). This
ensures that ongoing operation is not interrupted.
Содержание SIMATIC MV540 H
Страница 24: ...Description 1 7 Functional description SIMATIC MV500 24 Operating Instructions 06 2018 C79000 G8976 C494 01 ...
Страница 194: ...Service and maintenance 10 3 Replacing a module SIMATIC MV500 194 Operating Instructions 06 2018 C79000 G8976 C494 01 ...
Страница 232: ...Appendix A 3 Alternative user interfaces SIMATIC MV500 232 Operating Instructions 06 2018 C79000 G8976 C494 01 ...
Страница 236: ...List of abbreviations SIMATIC MV500 236 Operating Instructions 06 2018 C79000 G8976 C494 01 ...
Страница 238: ...Service Support SIMATIC MV500 238 Operating Instructions 06 2018 C79000 G8976 C494 01 ...