Oper
a
tin
g
line
Oper
a
tin
g
level
Func
tio
n
Defaul
t
val
ue
Min
Max
Unit
947
F
Flow temp setp incr hygro
10
−
−
−
/ 1
20
°C
948
I
Flow setp incr start at r.h.
60
0
100
%
950
I
Flow temp diff dewpoint
2
−
−
−
/ 0
5
°C
962
F
With buffer
No ¦ Yes
No
-
963
F
With prim contr/system pump
No ¦ Yes
No
-
969
F
Optg mode changeover
None ¦ Off ¦ Automatic
Off.
-
Heating circuit 2
1010 E
Comfort cooling setpoint
20.0
Operating line
1012
Operating line 1016 °C
1012 E
Reduced setpoint
19
Operating line
1014
Operating line 1010 °C
1014 E
Frost protection setpoint
10.0
4
Operating line 1012 °C
1016 F
Comfort setpoint max
35.0
Operating line
1010
35
°C
1020 E
Heating curve slope
0.8
0.10
4.00
-
1021 F
Heating curve displacement
0.0
-4.5
4.5
°C
1026 F
Heating curve adaption
Off ¦ On
Off.
-
1030 E
Summer/winter heating limit
18
−
−
−
/ 8
30
°C
1032 F
24-hour heating limit
-3
−
−
−
/ -10
10
°C
1040 I
Flow temp setpoint min
8
8
Operating line 1041 °C
1041 I
Flow temp setpoint max
80
Operating line
1040
95
°C
1050 F
Room influence
20
−
−
−
/ 1
100
%
1060 F
Room temperature limitation
1
−
−
−
/ 0.5
4
°C
1070 F
Boost heating
5
−
−
−
/ 0
20
°C
1080 F
Quick setback
Off ¦ Down to reduced setpoint ¦ Down to frost prot setpoint
Down to reduced setpoint
-
1090 F
Optimum start control max
0:00:00 00:00:00
00:06:00
h /min / s
1091 F
Optimum top control max
0:00:00 00:00:00
00:06:00
h /min / s
1100 F
Reduced setpoint increase start
−
−
−
−
−
−
/ -30
10
°C
1101 F
Reduced setpoint increase end
-15
-30
Operating line 1100 °C
1120 F
Overtemp prot pump circuit
Off ¦ On
On.
-
1130 F
Mixing valve boost
0
0
50
°C
1132 F
Actuator:type
2-position ¦ 3-position
3-position
-
1133 F
Switching differential
2-pos
2
0
20
°C
1134 F
Actuator running time
120
30
873
s
1150 I
Floor curing function
Off ¦ Functional heating ¦ Curing heating ¦ Functional/curing
heating¦ Curing/functional heating ¦ Manually
Off.
-
1151 E
Floor curing setpoint manually
25
0
95
°C
1156 E
Floor curing day current
−
−
−
0
32
°C
1157 I
Floor curing days complete
0
0
32
-
1161 F
Excess heat draw
Off ¦ Heating mode ¦ Always
Always
1170 F
With buffer
Yes
-
50/258
Siemens Switzerland Ltd
User manual RVS61.843, RVS41.813
CE1U2355en_02
HVAC Products