Buffer storage tank
Line no.
Operating line
5870
combi storage tank
No ¦ Yes
If, hydraulically, a combi storage tank is used, a partial diagram "Buffer" and partial
diagram "DHW" become active in the device software. This means that with the combi
storage tank, the functions are performed the same way as if buffer storage tank and
DHW storage tank were separate.
Exceptions:
The DHW request is always forwarded to the buffer storage tank, independent of the
setting for DHW storage tank with buffer. The DHW pump Q3 only starts when the
buffer sensor is also under the setpoint DHW – switching differential.
During the transfer, the DHW controlling element (Q3) will not be switched on. The
system allows a certain waiting time until the temperature levels are nearly the same.
Output relay QX
The use of relay outputs 1 to 6 can be individually selected.
Only RVS61..
Line no.
Operating line
5890
5891
5892
5894
5895
5896
Relay output QX1, QX2, QX3, QX4, QX5, QX6
None
Compressor stage 2 K2
Process revers valve Y22
Hot-gas temp K31
El imm heater 1 flow K25
El imm heater 2 flow K26
Diverting valve cool strat2 Y28
System pump Q14
Cascade pump Q25
Heat generator shutoff valve Y4
Electric immersion heater DHW K6
Circulating pump Q4
Storage tank transfer pump Q11
DHW intermediate circuit pump Q33
DHW mixing pump Q35
Collector pump Q5
Collector pump 2 Q16
Solar pump external exchanger K9
Solar controlling element buffer K8
Solar controlling element swimming pool K18
Electrical immersion heater buffer K16
H1 pump Q15
H2 pump Q18
H3 pump Q19
Heat circ pump HCP Q20
2. 2nd pump speed HC1 Q21
2. 2nd pump speed HC2 Q22
2. 2nd pump speed HCP Q23
Diverting valve cooling Y21
Air dehumidifier K29
Heat request K27
Refrigeration request K28
Alarm output K10
Time program 5 K13
174/258
Siemens Switzerland Ltd
User manual RVS61.843, RVS41.813
CE1U2355en_02
HVAC Products
6 The settings in detail