Oper
a
tin
g
line
Oper
a
tin
g
level
Func
tio
n
Defaul
t
val
ue
Min
Max
Unit
No ¦ Yes
1172 F
With primary controller / system pump
No ¦ Yes
Yes
1200 I
Optg mode changeover
None ¦ Protection ¦ Reduced ¦ Comfort ¦ Automatic
Protection
Heating circuit P
1300 E
Operating mode
Protection ¦ Automatic ¦ Reduced ¦ Comfort
Automatically
-
1310 E
Comfort cooling setpoint
20.0
Operating line
1312
Operating line 1316 °C
1312 E
Reduced setpoint
19
Operating line
1314
Operating line 1310 °C
1314 E
Frost protection setpoint
10.0
4
Operating line 1312 °C
1316 F
Comfort setpoint max
35.0
Operating line
1310
35
°C
1320 E
Heating curve slope
0.8
0.10
4.00
-
1321 F
Heating curve displacement
0.0
-4.5
4.5
°C
1326 F
Heating curve adaption
Off ¦ On
Off.
-
1330 E
Summer/winter heating limit
18
−
−
−
/ 8
30
°C
1332 F
24-hour heating limit
-3
−
−
−
/ -10
10
°C
1340 I
Flow temp setpoint min
8
8
Operating line 1341 °C
1341 I
Flow temp setpoint max
50
Operating line
1340
95
°C
1350 F
Room influence
20
−
−
−
/ 1
100
%
1360 F
Room temperature limitation
1
−
−
−
/ 0.5
4
°C
1370 F
Boost heating
−
−
−
−
−
−
/ 0
20
°C
1380 F
Quick setback
Off ¦ Down to reduced setpoint ¦ Down to frost prot
setpoint
Down to reduced setpoint
-
1390 F
Optimum start control max
0:00:00 00:00:00
00:06:00
h /min / s
1391 F
Optimum top control max
0:00:00 00:00:00
00:06:00
h /min / s
1400 F
Reduced setpoint increase start
−
−
−
−
−
−
/ -30
10
°C
1401 F
Reduced setpoint increase end
-15
-30
Operating line 1400 °C
1420 F
Overtemp prot pump circuit
Off ¦ On
Off.
-
1450 F
Floor curing function
Off ¦ Functional heating ¦ Curing heating ¦
Functional/curing heating¦ Manually
Off.
-
1451 F
Floor curing setpoint manually
25
0
95
°C
1455 E
Floor curing setpoint current
0
0
95
°C
1456 E
Floor curing day current
0
0
32
-
1457 I
Floor curing days complete
0
0
32
-
1461 F
Excess heat draw
Off ¦ Heating mode ¦ Always
Always
-
1470 F
With buffer
No ¦ Yes
Yes
-
1472 F
With primary controller / system pump
No ¦ Yes
Yes
-
1500 I
Optg mode changeover
None ¦ Protection ¦ Reduced ¦ Comfort ¦ Automatic
Protection
-
Domestic hot water
1610 E
Nominal setpoint
50
Operating line
TempBwMax
°C
51/258
Siemens Switzerland Ltd
User manual RVS61.843, RVS41.813
CE1U2355en_02
HVAC Products
5 Handling
28. September 2009