6 The settings in detail
28. September 2009
Line no.
Operating line
HC1
HC2
HCP
850
1150
1450
Floor curing function
Off
Functional heating
(Fh)
Curing heating
(Bh)
Functional/curing heating
Curing heating/functional heating
Manually
851
1151
1451
Floor curing setpoint manually
1455
Floor curing setpoint current
1456
Floor curing day current
1457
Floor curing days complete
Off:
Function is deactivated.
Functional heating
(Fh) :
The first part of the temperature profile is automatically completed.
Floor curing heating
(Bh)
The second part of the temperature profile is handled automatically.
Floor curing heating and functional heating
The entire temperature profile (first and second part) is handled automatically.
Manually
It is not a temperature profile that is completed, but the floor setpoint is controlled
manually. The function is automatically ended after 25 days.
The flow temperature setpoint for the "manual" floor curing function can be set
separately for each heating circuit.
Shows the current flow temperature setpoint of the running floor curing process.
Shows the current day of the running floor curing process.
If the floor curing process is terminated, the days completed are saved and retained
until the function is started the next time.
After a power failure, the plant resumes the floor curing function at the point in time the
power failure occurred.
In automatic operating modes, the controller ensures automatic completion of the
selected temperature profile.
50
45
40
35
30
20
5
10
15
18
[Tag]
0
25
55
Fh
Bh
1
1
5
7
X
Fh + Bh
1
25
23
58Z
10
[TVw]
Floor curing function
Floor curing setpoint
manually
Floor curing setpoint
current
Floor curing day current
Floor curing days
complete
Temperature profile