Oper
a
tin
g
line
Oper
a
tin
g
level
Func
tio
n
Defaul
t
val
ue
Min
Max
Unit
Off ¦ On
2951 I
Defrost release below OT
7
5
20
°C
2958 I
Numb defrost attempts max
3
0
10
-
2962 I
Duration defrost lock
30
0
100
min
2963 I
Time up to forced defrost
120
60
600
min
2964 I
Defrost time max
10
1
42
min
2965 I
Dripping time evapor
2
0
10
min
3000 I
Switch-off temp max cooling
40
20
60
°C
3002 F
Source temp min cool mode
2
-20
30
°C
3004 F
SD ch’over cooling pas/act
5
1
10
°C
3006 F
During compressor operation
Passive cooling off ¦ Passive cooling on
Passive cooling on
1
-
3007 F
In passive cooling mode
Condenser pump off ¦ Condenser pump on
Condenser pump off
1
-
3008 F
Temp diff cond cooling mode
5
0
20
°C
3030 F
Auto readj HP cond sensor
Off
¦ Now ¦ After pump prerun
Off.
-
3031 F
Readj HP flow sensor
0
-20
20
°C
3032 F
Readj HP return sensor
0
-20
20
°C
3033 F
Readj status
Not readjusted ¦ Manually readjusted ¦ Automatically
readjusted ¦ Readjustment running
Energy meter
3090 F
Pulse count heat
None With ¦ Input H1 ¦ With input H3
None
-
3092 F
Pulse unit heat
None ¦ kWh ¦ Liter
None
3093 F
Pulse unit heat numer
1
1
1000
-
3094 F
Pulse unit heat denom
1
1
1000
3097 F
Flow heating
---
10
60000
l/h
3098 F
Flow DHW
---
10
60000
l/h
3100 F
Pulse count energy
None With ¦ Input H1 ¦ With input H3
None
3102 F
Pulse unit energy
None ¦ kWh ¦ m3
None
3103 F1
Pulse value energy numer
1
1
1000
3104 F1
Pulse value energy denom
1
1
1000
3106 F2
Mean gas energy content
11.5
1
100
kWh/m3
3108 F1
Electric source output
---
0.1
10
kW
3110 F2
Heat delivered
0
0
9999999
kWh
3113 F2
Energy brought in
0
0
3500000
kWh
3116 F2
Performance factor
---
0
10
3119 F1
Fixed day yearly perf factor
30.6.
1.01
31.12
dd.MM
3120 E
Yearly perf factor 1
---
0
10
3120 E
Fixed day 1
1.9.2004
31.12.2099
dd.MM.y
yyy
3121 E
Heat delivered heating 1
0
0
9999999
kWh
3122 E
Heat delivered DHW 1
0
0
9999999
kWh
3124 E
Energy brought in heating 1
0
0
3500000
kWh
3125 E
Energy brought in DHW 1
0
0
3500000
kWh
3127 E
Yearly perf factor 2
---
0
10
54/258
Siemens Switzerland Ltd
User manual RVS61.843, RVS41.813
CE1U2355en_02
HVAC Products
5 Handling
28. September 2009