Technical data
8.1 Basic units RVS61.843 and RVS41.813
Rated voltage
AC 230 V (+10% / -15%)
Bemessungsfrequenz
50/60 Hz
Power consumption
max. 11 VA
Fusing of supply lines
Automatic cutout: Max. 13 A to EN 60898-1
Fuse: Max. 10 AT
Power supply
(Power supply and outputs)
solid wire or stranded wire (twisted or with
ferrule):
1 core: 0.5 mm
2
…2.5 mm
2
2 cores 0.5...1.5 mm
2
Wiring of terminals
Software class
A
Mode of operation to EN 60 730
1b (automatic operation)
Functional data
Digital inputs H1, H3
safety extra low-voltage for potentialfree low-
voltage contacts:
voltage with contact open: DC 12 V
current with contact closed: DC 3 mA
Analog input H1, H3
protective extra low-voltage operating range: DC
(0…10) V
internal resistance: > 100 k
Ω
Mains inputs EX1 – EX7,
E9 – E11
AC 230 V (
±
10 %)
internal resistance: > 100 k
Ω
Sensor input B9
Sensor inuts B1, B3, B4, B21, B41,
B71, B81, B91 and B92
NTC1k (QAC34)
NTC 10k (QAZ36, QAD36)
Sensor input BX1 – BX5
NTC10k (QAZ36, QAD36), Pt1000
Perm. Sensor cables (copper)
−
Cross-sectional area:
0.25 0.5
0.75 1.0
1.5 (mm2)
−
Max. length:
20
40
60
80
120 (m)
Inputs
Relay outputs Q2, 3, 8,9, Qx1..6, Y1,
Y2
Rated current range
Max. switch-on current
Max. total current (all relays)
Rated voltage range
AC 0.02…2 (2) A
15 A for
≤
1 s
AC 10 A
AC (24..230) V (for potentialfree outputs)
Output Q4-Mod
Rated current range
On / off mode
Speed control
Max. switch-on current
AC 0.05…2 (2) A
AC 0.05…0.4 (1) A
4 A for
≤
1 s
Analog output U1
Output voltage
Current rating
Ripple
Accuracy at zero point
Error remaining range
output is shortcircuit-proof
U
out
= 0 ... 10.0 V
±2 mA RMS; ±2.7 mA peak
50 mVpp
< ± 80 mV
130 mV
Outputs
242/258
Siemens Switzerland Ltd
User manual RVS61.843, RVS41.813
CE1U2355en_02
HVAC Products
8 Technical data