Sensors
Line no.
Operating line
6200
Save sensors
At midnight, the basic unit saves the states at the sensor terminals, provided the
controller has previously been in operation for at least 2 hours.
If, after storage, a sensor fails, the basic unit generates an error message.
This setting is used to ensure immediate saving of the sensors. This is necessary
when, for instance, a sensor is removed because it is no longer needed.
Line no.
Operating line
6201
Reset sensors
This setting is used to reset all connected sensors. The sensors are read in again using
function "Save sensors" (6200), or automatically at midnight, provided the controller
has previously been in operation for at least 2 hours.
Parameters
Line no.
Operating line
6204
Save parameters
The current parameter settings can be saved as new default settings. Exempted from
this are the following menus: Time of day and date, operator section, wireless, and all
time programs, as well as the number of operating hours and the different meters.
Important:
With this process, the factory settings will be overwritten and cannot be retrieved!
Line no.
Operating line
6205
Reset to default parameters
The parameters can be reset to their default values. Exempted from this are the
following menus: "Time of day and date", Operator section", "RF", and all time
programs, as well as the number of operating hours and the different counters.
Plant diagram
Line no.
Operating line
6212
Check no. heat source 1
Solar
XX
6213
Check no. heat source 2
Heat pump
XX
6215
Check-No. storage tank
combi storage tank
Buffer storage tank
DHW storage tank
XX
XX
XX
6217
Check no. heating circuit
Heating circuit P
Heating circuit 2
Heating circuit 1
XX
XX
XX
195/258
Siemens Switzerland Ltd
User manual RVS61.843, RVS41.813
CE1U2355en_02