Recooling
Line no.
Operating line
4755
Recooling temp
4756
Recooling DHW/HCs
4757
Recooling collector
Off.
Summer
Always
If the buffer storage tank had to be charged via "Charging temp max", recooling to the
recooling temperature set here takes place as soon as possible.
Recooling temp
For recooling the buffer storage tank, the 2 following functions are available:
The heat energy can be drawn off either by space heating or the DHW storage tank.
The function is activated or deactivated on this operating line. This can be selected
separately for each heating circuit (menu "Heating circuit 1…").
Recooling DHW/HCs
When the collector is cold, the energy can be emitted to the environment via the
collector’s surfaces.
Recooling collector
Off.
Recooling via the collector is deactivated.
Summer
Recooling via the collector is permitted in summer only.
Always
Recooling via the collector is activated throughout the year.
Electric immersion heater
Line no.
Operating line
4760
Charg sensor el imm heater
4761
Forced charging electric
The electric immersion heater
in the buffer storage tank
is released for forced
charging when none of the heat sources is able to deliver heat, and in the case of
active frost protection for the buffer storage tank.
The electric immersion heater
in the flow
is switched on for forced charging if the heat
pump does not reach the setpoint and if, on operating line 2880, "Use electric flow",
setting "Complement HP operation" is used, or when the heat pump works in
emergency operation and on operating line 2880, "Use electric flow", setting
"Substitute" is used.
This defines the sensor to be used for charging with an electric immersion heater.
Charg sensor el imm
heater
B4
The electric immersion heater is switched on and off via sensor B4.
B42 / B41
The electric immersion heater is switched on via sensor B41 and off via sensor B42.
If, within one minute after triggering forced charging, none of the heat sources in the
system is put into operation for forced charging of the buffer storage tank, the electric
immersion heater can ensure it.
Forced charging electric
No
Electric immersion heater K16 is not used for forced charging.
160/258
Siemens Switzerland Ltd
User manual RVS61.843, RVS41.813
CE1U2355en_02
HVAC Products
6 The settings in detail
28. September 2009