Oper
a
tin
g
line
Oper
a
tin
g
level
Func
tio
n
Defaul
t
val
ue
Min
Max
Unit
1612
1612 E
Reduced setpoint
40
8
Operating line 1610 °C
1620 I
Release
24h/day ¦ Time programs HCs ¦ Time program 4 / DHW ¦
Low-tariff ¦ Time prog 4/DHW or LT
Time program 4 / DHW
-
1620 I
Release
24h/day ¦ Time programs HCs ¦ Time program 4 / DHW
Time program 4 / DHW
-
1630 I
Charging priority
Absolute ¦ Shifting ¦ None ¦ MC shifting, PC absolute
Absolute
-
1640 F
Legionella function
Off ¦ Periodically ¦ Fixed weekday
Off.
-
1641 F
Legionella funct periodically
3
1
7
Days
1642 F
Legionella funct weekday
Monday ¦ Tuesday ¦ Wednesday ¦ Thursday ¦ Friday ¦
Saturday ¦ Sunday
-
1644 F
Legionella func time
−
−
−
−
−
−
/ 00:00
23:50
hh:mm
1645 F
Legionella func setpoint
65
55
95
°C
1646 F
Legionella funct duration
30
−
−
−
/ 10
360
min
1647 F
Legionella funct circ pump
Off ¦ On
On.
-
1660 F
Circulating pump release
Time program 3 / HCP ¦ DHW release ¦ Time program 4 /
DHW ¦ Time program 5
Time program 3 / HCP
-
1661 F
Circulating pump cycling
Off ¦ On
Off.
-
1663 F
Circulation setpoint
45
8
80
°C
Pump Hx
2010 F
H1 Excess heat draw
Off ¦ On*
On.
-
2012 F
H1 with buffer
No ¦ Yes*
Yes
-
2014 F
H1 prim contr/system pump
No ¦ Yes*
Yes
-
2015 F
H1 Refrigeration request
2-pipe system* ¦ 4-pipe system
2-pipe system
-
2035 F
H2 Excess heat draw
Off ¦ On*
On.
-
2037 F
H2 with buffer
No ¦ Yes*
Yes
-
2039 F
H2 prim contr/system pump
No ¦ Yes*
Yes
-
2040 F
H2 Refrigeration request
2-pipe system* ¦ 4-pipe system
2-pipe system
-
2046 F
H3 Excess heat draw
Off ¦ On*
On.
-
2048 F
H3 with buffer
No ¦ Yes*
Yes
-
2050 F
H3 prim contr/system pump
No ¦ Yes*
Yes
-
2051 F
H3 Refrigeration request
2-pipe system ¦ 4-pipe-system
2-pipe system
-
Swimming pool
2055 E
Setpoint solar heating
26
8
80
°C
2056 E
Setpoint source heating
22
8
80
°C
2065 F
Charging priority solar
No ¦ Yes
No
-
6)
6)
6)
6)
52/258
Siemens Switzerland Ltd
User manual RVS61.843, RVS41.813
CE1U2355en_02
HVAC Products
5 Handling
28. September 2009