10V output UX
Line no.
Operating line
6070
Function output UX
Only RVS61..
Only RVS41..
None
Source pump Q8 / fan K19
DHW pump Q3
DHW interm circ pump Q33
Instant DHW heater Q34
Collector pump Q5
Collector pump 2 Q16
Solar pump buffer K8
Solar pump external exchanger
K9
Solar pump swi pool K18
Heating circuit pump HC1 Q2
Heat circuit pump HC2 Q6
Heat circuit pump HCP Q20
HP setpoint
Output setpoint
Heat request
Refrigeration request
None
Source pump Q8 / fan K19
Collector pump Q5
Solar pump buffer K8
HP setpoint
Output setpoint
Heat request
Refrigeration request
Solar pump external exchanger
K9
Solar pump swi pool K18
6071
Signal logic output UX
Standard
Inverted
6072
Signal output UX
0..0.10V
PWM
6075
Temp value 10V UX
The voltage-modulated output can be used either for speed-controlled pumps or as an
output for a voltage-proportional temperature request.
Function output UX
Speed-controlled pump
The output signal at UX corresponds to the speed required for the selected pump.
Heat pump setpoint:
The output signal at UX corresponds to the heat pump setpoint for heating or
cooling.
Output setpoint:
The output signal at UX is proportional to the demand for output on the common
flow.
Heating and cooling request:
The output signal at UX corresponds to the common flow temperature setpoint.
The voltage signal can be inverted. It can thus also be used to control pumps with
Signal logic output UX
variable speeds, or temperature request receivers that use inverted signal logic.
Determines whether the signal shall be delivered as a DC 0...10 V signal or pulse
width-modulated signal (PWM).
Signal output UX
This operating line is used to define the maximum temperature request
Temp value 10V UX
(corresponding to 10 V).
192/258
Siemens Switzerland Ltd
User manual RVS61.843, RVS41.813
CE1U2355en_02
HVAC Products
6 The settings in detail
28. September 2009