Line no.
Operating line
7700
Relay test
Only RVS61..
Only RVS41..
No test
Everything off
Source pump Q8 / fan K19
Compressor K1 (for approx. 1
– 2 s.)
Condenser pump Q9
DHW pump Q3
Heating circuit pump 1
Heating circ mix valve op Y1
Heat circ mix valve cl Y2
Relay output QX23 module 1
Relay output QX21 module 1
Relay output QX22 module 1
Relay output QX1
Relay output QX2
Relay output QX3
Relay output QX4
Relay output QX5
Relay output QX6
Relay output QX23 module 2
Relay output QX21 module 2
Relay output QX22 module 2
No test
Everything off
Relay output QX23 module 1
Relay output QX21 module 1
Relay output QX22 module 1
Relay output QX1
Relay output QX2
Relay output QX3
Relay output QX4
Relay output QX5
Relay output QX6
Relay output QX23 module 2
Relay output QX21 module 2
Relay output QX22 module 2
Relay output QX7
Relay output QX8
Important:
During the relay test, limitations are not active.
Only RVS41..
When using a multifunctional output for compressor K1, the output will be disabled
for about 1 to 2 seconds.
Output test UX
By selecting a setting from output test UX / P1, an appropriate signal is delivered,
enabling it to be checked.
Line no.
Operating line
7710
Output test UX
7711
Voltage signal UX
7714
PWM signal P1
Input test sensors
By selecting a setting from input test sensors, the relevant input is displayed, enabling it
to be checked.
Line no.
Operating line
7730
Outside temp B9
7732
Flow temp B1
7750
DHW temp B3
7770
Flow temp HP B21
7771
Return temp HP B71
7772
Hot-gas temp B81
7775
Source inlet temp B91
7777
Sensor temp B92, B84
7820
Sensor temp BX1
7821
Sensor temp BX2
7822
Sensor temp BX3
7823
Sensor temp BX4
7824
Sensor temp BX 5
7830
Sensor temp BX21 module 1
7831
Sensor temp BX22 module 1
7832
Sensor temp BX21 module 2
7833
Sensor temp BX22 module 2
Only RVS61..
Only RVS61..
The selected sensor values are updated within a maximum of 5 seconds.
The display is made with no measured value correction.
211/258
Siemens Switzerland Ltd
User manual RVS61.843, RVS41.813
CE1U2355en_02
HVAC Products
6 The settings in detail
28. September 2009