220
System Manual V2 – MOVITRAC® B
10
Return codes (r-19 ... r-38)
Operation
10.1.4 Data backup using MOVITOOLS
®
MotionStudio
When you use MOVITOOLS
®
MotionStudio to transfer data to the MOVITRAC
®
B
frequency inverter, you must re-enable the inverter as follows:
•
Select the unit in the network.
•
Right click to open the context menu.
•
Select menu [RUN/STOP via software keypad] [1]
•
Select [RUN] in the software keypad [2]
10.2
Return codes (r-19 ... r-38)
Return codes MOVITRAC
®
B:
[1]
[2]
No.
Designation
Meaning
19
Parameter lock activated
Parameters cannot be changed
20
Factory setting in progress
Parameters cannot be changed
23
Option card missing
The option card required for the function is missing.
27
Option card missing
The option card required for the function is missing.
28
Controller inhibit required
Controller inhibit required
29
Invalid value for parameter.
•
Invalid value for parameter.
•
FGB manual operation selection invalid as PC is
in active manual operation.
32
Enable
You cannot perform this function in ENABLED status
34
Fault during execution
•
Error while saving in FBG11B.
•
Startup not performed with FBG. Perform FGB
startup with MotionStudio or select a new motor.
38
FBG11B incorrect data set
Stored data set does not match the unit
0
0
I