System Manual V2 – MOVITRAC® B
9
Startup with DBG60B
Startup
4. To startup, select the OK key. The first parameter appears.
The flashing cursor under the parameter number indicates
that the keypad is in display mode.
•
Use the
↔
key to switch to edit mode. The flashing
cursor disappears.
•
Use the
↑
or
↓
key to select "PARAMETER SET 1" or
"PARAMETER SET 2".
•
Press the OK key to confirm your selection.
•
Use the
↔
key to switch back to display mode. The
flashing cursor appears again.
•
Use the
↑
key to choose the next parameter.
STARTUP
PREPARE FOR STAR-
TUP
C00*STARTUP
PARAMETER SET 1
PARAMETER SET 2
5. Set the motor type.
C22*MOTORS
SINGLE MOTOR
IDENT. MOTORS
DIFFERENT MOTORS
6. Select the operating mode you require. Use the
↑
key to
choose the next parameter.
VFC operating mode is required for activating the flying
start or hoist function.
C01*OPER. MODE 1
STANDARD V/f
VFC1
a. When selecting STANDARD V/f operating mode:
C28*DC BRAKING
NO
YES
b. When selecting VFC operating mode:
C36*OPER.MODE
SPEED CONTROL
HOIST
DC BRAKING
FLYING START
7. Select the motor type. If a 2 or 4-pole SEW motor is
connected, select the correct motor from the list. If a non-
SEW motor or an SEW motor with more than four poles is
connected, select "NON-SEW MOTOR" from the list.
Use the
↑
key to choose the next parameter.
C02*MOTOR TYPE 1
DT71D2
DT71D4
DT80K2
C02*MOTOR TYPE 1
NON-SEW MOTOR
DT63K4/DR63S4
0
0
I