Application examples
Project Planning
Terminals
•
Rapid speed: DI04 = 1 and DI05 = 1
•
Slow speed: DI04 = 1 and DI05 = 0
Assign the electronics terminal strip with
•
DI01 = CW/stop
•
DI02 = CCW/Stop
•
DI03 = Enable
•
DO01-C and DO01-NO = "Fault"
•
DO02 = Brake
K1 is the brake contactor, S1 the fault indicator light.
The following signals between the machine controller PLC and MOVITRAC
®
B are
important:
Parameters
The following parameters are relevant for this application. Check whether you can leave
all factory setting values unchanged.
X12:2: Clockwise direction of rotation
X12:6: Slow speed/rapid speed
X12:3: Counterclockwise direction of rotation
X12:8: 24 V
X12:4: Start/Stop
X13:6: No malfunction
X12:5: Rapid speed
X13:2: Brake released
1
2
3
4
DI00
DI01
DI02
DI03
X12:
5
6
7
8
DI04
DI05TF
VOTF
24VIO
9
GND
1
2
3
4
GND
DO02
DO03
GND
X13:
5
6
7
DO01-C
DO01-NO
DO01-NC
K1
PLC
S1
P601 Binary input DI02: CCW/stop
P604 Binary input DI05: n12/n22
P602 Binary input DI03: Enable
P620 Binary output DO01: Malfunction
P603 Binary input DI04: n11/n21
P621 Binary output DO02: Brake released