88
System Manual V2 – MOVITRAC® B
5
Explanation of the parameters
Parameters
08_
Fault memory
080 ...
084
Fault t-0 ... Fault t-4 (FBG11B
keypad: fault t-0 only)
The unit saves the following information when an error occurs. MOVITOOLS
®
MotionStudio can display this information if required:
•
P036/P053 Status of binary inputs/binary outputs
•
P013 Current parameter set
•
P011 Operating status of the inverter
•
P010 Inverter status
•
P014 Heat sink temperature
•
P000 Speed
•
P004 Output current
•
P005 Active current
•
Unit utilization
•
P008 DC link voltage
09_
Bus diagnostics
094
PO 1 Setpoint [hex]
Process data output word 1, setpoint
095
PO 2 Setpoint [hex]
Process data output word 2, setpoint
096
PO 3 Setpoint [hex]
Process data output word 3, setpoint
097
PI 1 Actual value [hex]
Process data input word 1, actual value
098
PI 2 Actual value [hex]
Process data input word 2, actual value
099
PI 3 Actual value [hex]
Process data input word 3, actual value
1__
Setpoints/ramp generators
10_
Setpoint selection/frequency input
100
Setpoint source
0 / Bipolar / Fixed setpoint
The setpoint is provided by the analog input or the fixed setpoints. The unit
processes the fixed setpoints according to their value.
The speed is limited by the maximum set speed P302/P312 in the event of
a wire breakage.
1 / Unipolar / Fixed setpoint
The setpoint is provided by the analog input or the fixed setpoints. The unit
processes the fixed setpoints
according to their value
. The binary inputs
specify the direction of rotation.
2/ RS-485 / Fixed setpoint
The setpoint is provided by the RS-485 interface. The sign of the setpoint
determines the direction of rotation.
4 / Motor potentiometer / Fixed setpoint
Set the setpoint by programming the terminals
Motor potentiometer up
and
Motor potentiometer down
accordingly. The motor potentiometer is a virtual
potentiometer that does not correspond to the setpoint potentiometer on the
unit.
6 / Fixed se AI1
The setpoint is calculated by adding the selected fixed setpoint and analog
input AI1. The binary inputs specify the direction of rotation. Furthermore,
P112 AI1 operation mode
applies.
7 / Fixed setpoint * AI1
The value at the analog input AI1 serves as an evaluation factor for the
selected fixed setpoint (0 ... 10 V = 0 ... 100 %). If no fixed setpoint is
selected, n
min
applies. The binary inputs specify the direction of rotation.
8 / MASTER SBus1
In master/slave mode, the setpoint is provided by the master via system bus
1. See P75x master/slave function.
9 / MASTER RS-485
The setpoint is provided by the master in master/slave mode via the RS-485
interface. See P75x master/slave function.
10 / SBus 1 / Fixed setpoint
The system bus specifies the setpoint. The sign of the setpoint determines
the direction of rotation.
No.
FBG
Name
Description
P
i
f
kVA
Hz
n
Содержание MOVITRAC MC07B0037-2A3-4-00