System Manual V2 – MOVITRAC® B
8
Installing FSC11B / FIO11B
Installation
The DC 24 V function of X46:7 is identical to X12:8 of the basic unit. All GND terminals
of the unit are connected to each other and to PE.
Analog
output
X40:3
GND: Reference
potential
0 ... +10 V
I
max
= 2 mA
0 (4) ... 20 mA
Resolution 10 bit
Sampling time 5 ms
Short-circuit proof,
protected against
external voltage up to
30 V
No
Yes
X40:4
AOV1: Voltage output
X40:5
AOI1: Current output
Function
Termi-
nal
Description
Data
FSC11B
FIO11B
Cable specification
•
Use a 4-core twisted and shielded copper cable (data transmission cable with braided
copper shield). The cable must meet the following specifications:
–
Core cross section 0.25 ... 0.75 mm
2
(AWG 23 ... AWG 18)
–
Cable resistance 120 at 1 MHz
–
Capacitance per unit length
≤
40 pF/m at 1 kHz
Suitable cables include CAN bus or DeviceNet cables.
Connecting the shield
•
Connect the shield to the electronics shield clamp on the inverter or master controller and
make sure it is connected over a wide area at both ends.
•
There is no need for a ground connections between MOVITRAC
®
B and gateways, or
MOVITRAC
®
B and MOVITRAC
®
B with shielded cables. A 2-core cable is permitted in this
case.
•
When connecting MOVIDRIVE
®
B and MOVITRAC
®
B, be aware that the electrical isola-
tion is eliminated between the reference potential DGND and ground in MOVIDRIVE
®
B.
STOP!
Potential displacement
Possible consequences include malfunctions that could lead to irreparable damage to
the unit.
•
There must not be any potential displacement between the connected units. Take
appropriate measures to avoid potential displacement, such as connecting the
unit ground connectors using a separate cable.