System Manual V2 – MOVITRAC® B
43
4
FIO11B analog module
Technical Data
4.7
FIO11B analog module
Part number 1820 637 9
4.7.1
Description
The FIO11B analog module adds the following interfaces to the basic version:
•
Setpoint input
•
Analog output
•
RS-485 interface
•
The options FIO11B and FSC11B are mounted on the same fastening place and
therefore cannot be used simultaneously.
4.7.2
Electronics data FIO11B analog module
X45 X40
1 2 3 4 5
H L
A
FIO11B
X44
Function
Terminal
Designation
Data
Setpoint input
1)
1) If the setpoint input is not used, it should be set to GND. Otherwise a measured input voltage of –1 V ... +1 V is set.
X40:1
X40:2
AI2: Voltage input
GND: Reference potential
–10 ... +10 V
R
i
> 40 k
Resolution 10 bit
Sampling time 5 ms
Analog output/
alternative as cur-
rent output or volt-
age output
X40:3
X40:4
X40:5
GND: Reference potential
AOV1: Voltage output
AOC1: Current output
0 ... +10 V / I
max
= 2 mA
0 (4) ... 20 mA
Resolution 10 bit
Sampling time 5 ms
Short-circuit proof, protected against external voltage up
to 30 V
Load impedance R
L
≤ 750 Ω
RS-485 interface
X45:H
X45:L
X
45:⊥
ST11: RS-485+
ST12: RS-485–
GND: Reference potential
EIA standard, 9.6 kbaud, max. 32 stations
Maximum cable length 200 m (656 ft)
Dynamic terminating resistor with fixed installation
Terminal cross-section:
–
1.5 mm
2
(AWG15) without conductor end sleeves
–
1.0 mm
2
(AWG17) with conductor end sleeves
X44
RJ10
Service interface
Connection: Only for service purposes, exclusively for
point-to-point connection
Maximum cable length 5 m (20 ft)
P
i
f
kVA
Hz
n
Содержание MOVITRAC MC07B0037-2A3-4-00