System Manual V2 – MOVITRAC® B
141
6
Parameter set switchover
Project Planning
6.17
Parameter set switchover
This function is used to operate two motors on one inverter using two different parameter
sets.
The parameter set is switched over via binary input or fieldbus. A binary input must be
programmed to the "Parameter set switchover" function
(→
P60_/P61_) for this
purpose. You can then change from parameter set 1 to 2 and vice versa in INHIBITED
inverter status.
Function
Effect at
"0" signal
"1" signal
PARAM. SELECT
Parameter set 1 active
Parameter set 2 active
NOTE
A changeover contactor should be provided for each of the two motor cables when two
motors are operated alternately on the same inverter with the parameter set
switchover function in use. Only switch changeover contactors when the unit is
inhibited!