System Manual V2 – MOVITRAC® B
89
5
Explanation of the parameters
Parameters
100
Setpoint source
11 / Frequency setpoint input / Fixed setpoint
The frequency at binary input DI04 specifies the setpoint. Set the value with
the
P102 Frequency scaling
parameter. You can influence the value with
P110 AI1 scaling
. The following parameters are included in the scaling if the
PI controller is activated:
•
P254 PI actual value scaling
•
P255 PI actual value offset
The optimum pulse duty factor (pulse width of the high and low signal)
should be 1 : 1. The factor determines the rising edge and the falling edge
of the input signal. Use P102 Frequency scaling to determine at which input
frequency the system setpoint 100 % is reached. The reference of the sys-
tem setpoint is set via P112 AI1 Operating mode. The direction of rotation is
set via the binary inputs CW/STOP and CCW/STOP.
Frequency scaling Minimum response time Resolution
(delay)
Frequency input
25 ... 120 kHz
20 ms
50 Hz
12.5 ... 24.99 kHz
40 ms
25 Hz
10 ... 12.49 kHz
60 ms
16.7 Hz
1 ... 9.99 kHz
500 ms
2 Hz
Setpoint cascade
P302: Maximum speed in rpm
P110: Gain 0.1 ... 1 ... 10
P102: Frequency scaling 1 ... 120 kHz
P112: Operation mode setpoint
Example:
A setpoint generator with the value range 1 ... 50 kHz is to set the motor
speed of 30 ... 1500 rpm.
Set the following parameters for this:
•
P102 Frequency scaling: 50 kHz
•
P112 Operation mode setpoint: 3000 rpm
•
Setpoint scaling P110: 0.5
14 / Bipolar AI2 / Fixed setpoint
The setpoint is provided by the optional analog input AI2 or the fixed
setpoints. The unit processes the fixed setpoints according to their value.
No.
FBG
Name
Description
DI04
P110
P102
·
P302
·
f
P112
P100
3000
· rpm
P
i
f
kVA
Hz
n