-48 VDC Remote Power Manager
Advanced Operations
117
Installation and Operations Manual
Change Trap
The Change trap is generated for all outlet status changes between any on/off conditions. Change traps include the
outlet status, location of the unit, and identifier/name of the affected outlet. For descriptions of the outlet status types,
refer to the previous table.
Load Trap
The Load trap is generated whenever the total load on an outlet exceeds a preset threshold. Load traps include the
reported load, load status, location of the unit, and identifier/name of the affected outlet.
Any error state generates a load trap and triggers the trap timer. A new trap is generated at the end of every timer period
until the load returns to a non-error status.
Load Traps
Status
Error
Description
Normal
Outlet is on and within preset thresholds
NotOn
Outlet is off
Reading
Non-error state
– Load status currently being read
LoadHigh
x
Outlet current load exceeds preset threshold
OverLoad
x
Outlet current load exceeds the measurable range for the infeed
ReadError
x
Unable to read Load status
NoComm
x
Communication to the infeed has been lost
Temp Trap
The Temp trap is generated whenever the temperature on a temperature/humidity sensor is beyond preset thresholds.
Temp traps include the reported temperature, temp status, location of the unit, and identifier/name of the affected
sensor.
Any error state generates a temp trap and triggers the trap timer. A new trap is generated at the end of every timer period
until the temp returns to a non-error status.
Temp Traps
Status
Error
Description
Normal
The sensor is working correctly and the temperature is within preset thresholds
NotFound
No sensor has been detected
Reading
Temp status currently being read
TempLow
x
Temperature at the sensor below preset low threshold
TempHigh
x
Temperature at the sensor exceeds preset high threshold
ReadError
x
Unable to read Temp status
Lost
x
Sensor initially detected but communication to the sensor has been lost
NoComm
x
Communication to the sensor has been lost
Humidity Trap
The Humidity trap is generated whenever the humidity on a temperature/humidity sensor is beyond preset thresholds.
Humidity traps include the reported relative humidity, humidity status, location of the unit, and identifier/name of the
sensor.
Any error state generates a humidity trap and triggers the trap timer. A new trap is generated at the end of every timer
period until the humidity returns to a non-error status.