-48 VDC Remote Power Manager
Installation and Operations Manual
Enabling or disabling Environmental Monitor traps:
Click on the
Environmental Monitor Traps
link.
On the subsequent page, select or deselect the desired traps and click
Apply.
Configuring Temperature and Relative Humidity sensor traps:
Click the
Sensor Traps and Thresholds
link.
On the subsequent Sensor Traps and Thresholds page, select or deselect the desired trap checkboxes and click
Apply.
Configuring Temperature and Relative Humidity sensor thresholds:
Click the
Sensor Traps and Thresholds
link.
For temperature thresholds, type a low and high temperature value in the Low Temp and High temp fields and click
Apply.
For relative humidity thresholds, type a low and high humidity percentage in the Low Humid and High Humid fields,
and click
Apply.
NOTE:
For temperature thresholds, the valid range is 0 to 123 in degrees Celsius or 32 to 254 in degrees Fahrenheit. For relative humidity,
the valid range is 0 to 100 (in percentage of relative humidity).
Configuring Temperature Recovery Delta:
Click the
Sensor Traps and Thresholds
link.
The Recovery Delta field allows configuration of the number of degrees of change needed to recover from a
temperature alarm. After exceeding the high-temperature threshold, the temperature value must fall below the high-
temperature threshold by the number of degrees specified in the Recovery Delta field before the sensor recovers.
For example, if the High Temp value is 80 degrees Fahrenheit, and the Recovery Delta field is 2 degrees Fahrenheit,
the sensor will not recover until a temperature value of 78 degrees Fahrenheit is reported.
To configure a temperature recovery delta, type a value (in degrees) in the Recovery Delta field and click
Apply.
NOTE:
The acceptable value range for the Recovery Delta field is 0-10 degrees for Celsius and 0-18 degrees for Fahrenheit. The default
value for the Recovery Delta field is 1 degree Celsius and 2 degrees Fahrenheit.