-48 VDC Remote Power Manager
Operations
77
Installation and Operations Manual
Setting the outlet wakeup state:
The Set Outlet Wakeup command set the default wakeup state for that outlet. In the event of a system-wide power
loss, this state will be applied to the outlet when power is restored.
The wakeup state can be set to On, Off or Last. Upon restoration of system power; If set to On, the unit will apply power to
that outlet. If set to Off, the unit will not apply power to that outlet. If set to Last, the unit will apply the last known power
state.
To set the wakeup state:
At the Switched -48 VDC: prompt, type
set outlet wakeup
, followed by
on
,
off
or
last
and the outlet name. Press
Enter
.
Example
The following command sets the wakeup state for outlet .aa1 to off:
Switched -48 VDC: set outlet wakeup off .aa1<Enter>
Setting the outlet locked (no control) state:
The Outlet Locked feature protects against accidental switching off of critical equipment that should rarely, if ever, be
relay-controlled. The feature also prevents unused outlets from being turned on, for example, when a circuit is at
capacity and additional devices/loads should not be turned on.
Control actions for a locked outlet will not be available in the CLI interface, and the outlet will not be affected by
group actions or Smart Load Shedding actions. SNMP control actions will be ignored for a locked outlet.
To set the outlet locked (no control) state:
At the Switched -48 VDC: prompt, type
set outlet locked
, followed by an outlet name, followed by
yes
, and press
Enter
.
Example
The following command locks outlet TowerA_InfeedA_Outlet1:
Switched -48 VDC: set outlet locked TowerA_InfeedA_Outlet1 yes<Enter>
When an outlet is configured into the locked state, the outlet will lock at its current control state (On or Off). The
outlet control state will then change to Locked On or Locked Off.
The locked control state (Yes or No) displays in the outlets list using the Show Outlets command:
Switched -48 VDC: show outlets<Enter>
Outlet Outlet Wakeup Post-On Locked
ID Name State Delay <sec> <No Control>
.AA1 TowerA_InfeedA_Outlet1 On 0
Yes
.AB1 TowerA_InfeedB_Outlet1 On 1
Yes
.AC1 TowerA_InfeedB_Outlet1 On 567
No
.AD1 TowerA_InfeedD_Outlet1 On 899
No