120
Advanced Operations
-48 VDC Remote Power Manager
Installation and Operations Manual
Enabling or Disabling the Temperature trap
The Set Trap THS Temp command enables or disables the Temperature trap.
To Enable or Disable the Temperature trap:
At the Switched -48 VDC: prompt, type
set trap ths temp
, followed by the sensor name and
on
or
off
. Press
Enter
.
Example
The following command enables the Temp trap for the first temperature-humidity sensor:
Switched -48 VDC: set trap ths temp .a1 on<Enter>
Setting the Temperature sensor threshold limits
The Set Trap THS Templow and Set Trap THS Temphigh commands are used to set the lower and upper threshold
limits for the Temperature sensor.
To set the Temperature threshold limits:
At the Switched -48 VDC: prompt, type
set trap ths
,
templow
or
temphigh
, followed by the sensor name and a value,
and press
Enter
.
Example
The following command sets the second temperature high threshold limit to 95:
Switched -48 VDC: set trap ths temphigh .a2 95<Enter>
The low and high ranges for the
templow
and
temphigh
fields are different, depending on the whether the tempscale
is set to Celsius or Fahrenheit. The following table defines the acceptable low and high ranges for each field.
Celsius
Fahrenheit
Field
Low
High
Low
High
TempLow
0
122
32
253
TempHigh
1
123
33
254
Enabling or Disabling the Humid trap
The Set Trap THS Humid command enables or disables the Humid trap.
To Enable or Disable the Humid trap:
At the Switched -48 VDC: prompt, type
set trap ths humid
, followed by the sensor name and
on
or
off
. Press
Enter
.
Example
The following command enables the Humid trap for the first temperature-humidity sensor:
Switched -48 VDC: set traps ths humid .a1 on<Enter>
Setting the Humidity sensor threshold limits
The Set Trap THS Humidlow and Set Trap THS Humidhigh commands are used to set the lower and upper threshold
limits for the Humidity sensor.
To set the Humidity threshold limits:
At the Switched -48 VDC: prompt, type
set trap ths
,
humidlow
or
humidhigh
, followed by the sensor name and a
value from 0 to 100 in percent relative humidity. Press
Enter
.
Example
The following command sets the first humidity sensor low threshold limit to 5:
Switched -48 VDC: set trap ths humidlow .a1 5<Enter>
The acceptable low and high ranges for the
humidlow
and
humidhigh
fields are defined in following table:
Humidity
Field
Low
High
HumidLow
0
99
HumidHigh
1
100