-48 VDC Remote Power Manager
Operations
101
Installation and Operations Manual
Changing the UPS host address:
The Set UPS Host command changes the IP address or hostname for each UPS record. Hostnames can be up to 60
characters long.
To change a UPS host address:
At the Switched -48 VDC: prompt, type
set ups host
and press
Enter
.
At the prompt, type the index number for the UPS record to be changed and press
Enter
.
At the prompt, type IP address or hostname for the UPS and press
Enter
.
Example
The following command changes UPS hostname for the record at index number 2 to ‘DC1Liebert1’:
Switched -48 VDC: set ups host<Enter>
1 Type: APC
Host/IP: DC1APC
2 Type: Liebert
Host/IP: DC1Liebert
Select UPS (1-11): 2<Enter>
Host/IP: DC1Liebert1<Enter>
Changing the UPS SNMP port:
With a UPS record configured, the CDU sends data requests to the default UPS SNMP port number 161. You can
change this port number using the Set UPS Port command.
To change the UPS SNMP port:
At the Switched -48 VDC: prompt, type
set ups port
and press
Enter
.
At the prompt, type the index number for the UPS record to be changed and press
Enter
.
At the prompt, type the desired port number and press
Enter
.
Example
The following command changes port for the UPS record at index number 1 to ‘162’:
Switched -48 VDC: set ups port<Enter>
UPS UPS
Index Type Port
1 APC 161
2 Liebert 161
Select UPS (1-11): 1<Enter>
Port: 162<Enter>
Changing the UPS SNMP Get community string:
With a UPS record configured, the CDI sends data requests to the UPS using the default Get community string of
‘public’. You can change this string using the Set UPS Commstr command.
NOTE:
The Get community string configured on the CDU
must
match the read-only community string configured on the UPS.
To change a UPS SNMP community string record:
At the Switched -48 VDC: prompt, type
set ups commstr
and press
Enter
.
At the prompt, type the index number for the UPS record to be changed and press
Enter
.
At the prompt, type the Get community string for the UPS and press
Enter
.
Example
The following command changes Get community string for the record at index number 2 to ‘readonly’:
Switched -48 VDC: set ups commstr<Enter>
UPS UPS Community
Index Type String
1 APC public
2 Liebert public
Select UPS (1-11): 2<Enter>
Community String: readonly<Enter>