-48 VDC Remote Power Manager
Installation and Operations Manual
To set a blank EnergyWise secret:
A blank secret is acceptable.
At the Switched -48 VDC: prompt, type
set energywise secret
, do not type in the Secret field, and press
Enter
twice
(to bypass the Secret field and then VerifySecret field.)
Example of a blank secret
Switched -48 VDC: show energywise
EnergyWise Configuration
Endpoint: Enabled *
Port: 666
Domain: (undefined)
Refresh Rate: 60
Secret: (Blank)
Command successful
To set the EnergyWise refresh rate:
The EnergyWise refresh rate is the rate (in seconds) at which new information is pushed to the EnergyWise manager.
Valid range is 30-600 seconds; default is new data sent to the EnergyWise manager every 3 minutes.
At the Switched -48 VDC: prompt, type
set energywise refresh
, followed by a rate (in seconds) from 30-600, and
press
Enter
.
Viewing Cisco EnergyWise network parameters:
NOTE:
A change in any value (shown in the example below) requires a restart of the system.
To view EnergyWise network parameters:
At the Switched -48 VDC: prompt, type
show energywise
, and press
Enter
.
Example
Switched -48 VDC: show energywise
EnergyWise Configuration
Endpoint: Enabled
Port: 43440
Domain: <undefined>
Refresh Rate: 180
Secret: <Blank>
Command successful