-48 VDC Remote Power Manager
Operations
103
Installation and Operations Manual
Displaying UPS status:
The UPSStat command displays the status of one or more UPS devices associated with the CDU.
The display includes UPS index number, type, line/battery status, and reported voltage.
NOTE:
Access to this command requires enabling user privileges for environmental monitoring using the Set User Envmon command.
To display status of one or more UPS devices:
At the Switched -48 VDC: prompt, type
upsstat
and press
Enter
.
Example
The following command displays the UPS status:
Switched -48 VDC: upsstat<Enter>
UPS UPS UPS UPS
Index Type Status Voltage
1 APC N/A N/A
2 Liebert On Battery 120.0
3 MGE On Utility 119.9