Details about Function Parameters
149
6.15 FU: Data Monitoring
FU-00
Working Frequency
Min. Unit
0.01Hz
Modification
△
Description Frequency x, reflecting the rotation speed of the motor
FU-01
Frequency Settings
Min. Unit
0.01Hz
Modification
△
Description Unit indicator lamp flashes
FU-02
Output Current
Min. Unit
0.1A
Modification
△
FU-03
Load Current Percentage
Min. Unit
0.1
%
Modification
△
Description The rated inverter current is taken as 100
%
FU-04
Output Voltage
Min. Unit
0.1V
Modification
△
FU-05
Rotation Speed
Min. Unit
1r/min
Modification
△
Description
FU-05 = 120×Working Frequency÷Number of Motor Poles×FC-13 “Rotation Speed
Display Coefficient”
FU-06
Rotation Speed Settings
Min. Unit
1r/min
Modification
△
Description
FU-06 = 120× Frequency Settings÷Number of Motor Poles×FC-13 “Rotation Speed
Display Coefficient”; Unit indicator lamp flashes
FU-07
DC Busbar Voltage
Min. Unit
0.1V
Modification
△
FU-08
Output Power
Min. Unit
0.1kW
Modification
△
FU-09
Working Linear Velocity
Min. Unit
1m/s
Modification
△
Description FU-09 “Working Linear Velocity”
=
Working Frequency×FC-14 “Linear Velocity
Display Coefficient”
FU-10
Linear Velocity Settings
Min. Unit
1m/s
Modification
△
Description FU-10 “Linear Velocity Settings”
=
Frequency Settings×FC-14 “Linear Velocity Display
Coefficient”; the Unit indicator lamp flashes
FU-11
PID Feedback Value
Min. Unit
-
Modification
△
FU-12
PID Settings
Min. Unit
-
Modification
△
FU-13
AI1
Min. Unit
0.1
%
Modification
△
FU-14
AI2
Min. Unit
0.1
%
Modification
△
FU-15
AI3
Min. Unit
0.1
%
Modification
△
FU-16
PFI
Min. Unit
0.1
%
Modification
△
FU-17
UP/DOWN Adjustment
Min. Unit
0.1
%
Modification
△
FU-18
Pump Status 1
Min. Unit
1
Modification
△
Description
Ten thousands digit: Pump #5 Thousands digit: Pump #4 Hundreds digit: Pump #3
Tens digit: Pump #2 Units digit: Pump #1
0: On standby 1: In variable-frequency operation 2: In line-frequency operation 3:
In fault overhaul
FU-19
Pump Status 2
Min. Unit
1
Modification
△
Description
Tens digit: Drainage pump Units digit: Sleeping pump
0: On standby 1: In variable-frequency operation 2: In line frequency operation 3:
In fault overhaul
FU-20
PID Output Value
Min. Unit
0.1
%
Modification
△
FU-21
Radiator Temperature
Min. Unit
0.1
o
C
Modification
△