Details about Function Parameters
89
F4-15
UP/DOWN Adjustment
Factory
Settings
0
Modification
○
Setting
Range
0: Terminal
Le vel mode
1:Terminal
pulse mode
2: Control panel
level mode
3: Control panel pulse
mode
F4-16
UP/DOWN Rated/Step Length
Factory
Settings
1.00
Modification
○
Setting
Range
0.01
~
100.00; min. settings: level mode: 0.01
%
/s; pulse mode 0.01
%
F4-17
UP/DOWN Memory Options
Factory
Settings
0
Modific
ation
○
Setting
Range
0:Storage on poweroff
1: Reset on poweroff
2: Reset on shutdown or poweroff
F4-18
UP/DOWN Upper Limit
Factory
Settings
100.0%
Modification
○
Setting
Range
0.0
~
100.0
%
F4-19
UP/DOWN Lower Limit
Factory
Settings
0.0%
Modification
○
Setting
Range
-100.0
~
0.0
%
The UP/DOWN function realizes continuous adjustment. The adjustment value can be used for
frequency settings and PID settings.
In the terminal level mode (F4-15
=
0),
when the digital input 19 (UP/DOWN: UP) or 20
(UP/DOWN: DOWN) is effective, FU-17 (UP/DOWN adjustment) will rise or fall at the rate set
by F4-16. When the digital inputs (19 and 20) are effective or ineffective at one time, the value of
FU-17 will remain unchanged.
In the terminal pulse mode (F4-15
=
1),
when each effective pulse is generated by digital input
19 “UP/DOWN: UP” or 20 (UP/DOWN: DOWN), FU-17 (UP/DOWN Adjustment) will rise or
fall by the step length set by F4-16.
F4-15
=
2 or 3 is similar to F4-15=0 or 1.
The difference is that in the former case,
and
on the control panel is used to substitute 19 and 20 (digital inputs). Only when FU-17
“UP/Down Adjustment” is displayed can adjustments be made with
and
.
Refer to the two control modes for UP/DOWN in the following figure: