Details about Function Parameters
82
±55: Priority pump
startup option 1
±56: Priority pump
startup option 2
±57: Priority pump
startup option 3
A negative value means that the terminal input is a high level or that the rising edge is effective.
A positive value means that the .terminal input has a low level, or that the falling edge is effective.
If the same function is selected via F4-00 through F4-12, the setting with the greater parameter
number is effective.
SB200 is inbuilt with 8 multifunctional programmable digital input terminals (X1, X2, X3, X4,
X5, X6, FWD and REV). Five other extension input terminals are also provided.
Functions in the table of digital input functions may be selected by the digital input terminal.
Also, the virtual input terminal, composed of the real-time clock module, can also be linked with
the digital input functions in the table. Refer to the description of F9 for details.
Related Monitoring Parameters: FU-25 (Digital Input Terminal Status 1) and FU-26 (Digital
Input Terminal Status 2)
Refer to the following detailed description of digital input functions:
0: Except when F4-05 = 0, connection of X6/PFI to other X terminals than PFI is
inapplicable.
1
~
3: Multi-Band Frequency Options: For coding, select Multi-Band Frequency 1—7.
Refer to the following table, where “0” means effective and “1” means ineffective:
Multi-Band
Frequency Option 3
Multi-Band
Frequency Option
2
Multi-Band
Frequency
Option 1
Multi-Band Frequency Selected
0 0
0
The frequency is set by the channel
selected via F0-01
0 0
1
F4-20 Multi-Band Frequency 1
0
1
0
F4-21 Multi-Band Frequency 2
0
1
1
F4-22 Multi-Band Frequency 3
1
0
0
F4-23Multi-Band Frequency 4
1 0
1
F4-24 Multi-Band Frequency 5
1
1
0
F4-25 Multi-Band Frequency 6
1
1
1
F4-26 Multi-Band Frequency 7
4
~
6: Check of Water Level of Clean Water Pool. Used for water shortage protection in
constant-pressure water supply. See the description of F80-3 on Page 72.
7:
Acceleration/Deceleration Time 2. If the signal is effective, select Acceleration/Deceleration
Time 2. Acceleration/deceleration time for jog and emergency shutdown is ineffective.
8
~
10: Multi-PID Options 1-3. The three terminals are used to select the present PID
settings via coding.